Survey Documentation Flashcards
Facility Layout
LS.01.01.01.03 - Current and Accurate Drawings, with fire safety features and related sq. footage.
*Areas fully sprinklered
*Locations of all hazardous storage areas
*Locations of all fire-rated barriers
*Locations of all smoke-rated barriers
*Sleeping and non-sleeping suite boundaries
*Locations of designated smoke compartments
*Locations of chutes and shafts
*Any approved equivalencies or waivers
Life Safety Code Waivers
Building Occupancy Permits
State / Local fire inspections
Policies
Fire Watch, Smoking, Space heater, etc.
In Services
Certificates
Boilers, Elevators
Exit signs
Monthly
Emergency Lighting and Battery function
Monthly 30 sec., Annual 90 min.
Exit lighting
Monthly
Magnetic door hold-open locking devices
Quarterly
Delayed egress door
Monthly
Locking Doors
Monthly
Corridor smoke doors
Annually
Fire door testing
Annually
Elevator ITM - Inspection, Testing, Maintenance
Monthly/Quarterly/Annually
HVAC ITM
Manufacturer’s recommendations,
Monthly/Quarterly/Annually
Fire and Smoke damper inspections
ITM every 4-years
https://www.youtube.com/watch?v=ZuceeixgEuU
Good overview, non all-encompassing
Sprinkler system
Quarterly / Annual
Inspection done IAW
NFPA 101-2012 LSC
NFPA 72 2010 Fire alarm systems
NFPA 25 2011 Water-Based fire protection systems
Company: Brewer and Company, Inspector Les Wilson
Sprinkler system (wet) pressure gauge reading. As well as (dry).
W monthly D weekly
Sprinkler System inventory
Needs documented
Spare Sprinkler Heads
Quarterly
Sprinkler inspections, head, backflow, antifreeze
Annual
Sprinkler Dry pressure system check
Triennial
Standpipe system
Triennial
Fire pump ITM (Electric/diesel testing is also needed documents)
Annual and electric - monthly, diesel - weekly for operations inspections
Fire pump inspections
Weekly
Kitchen range hood system and suppression system & cleaning
Semi-annual ITM, monthly
Fire Alarm testing
semi-annual and annual
Smoke detectors
at 1 year and every two years thereafter
Portable fire extinguishers
Monthly / Annual
Fire Drills
One / month (per shift / per - quarter)
Fire hydrants
Annual
Smoke barrier inspections
recommended quarterly
Electrical ITMs
Documented
Ground fault receptacles (GFIs)
recommended quarterly
non-hospital grade
Annual
PCREE electrical equipment
Annual
General Preventative Maintenance
Annual
Generator
Weekly, Monthly, Load Bank annual. 36-month load exercise.
Generator diesel fuel testing
Annual
Fuel reliability letter
not sure of the req.