Summary of P's and C's Flashcards

1
Q

List all Protection premissives

A

1: P-4 Reactor Trip Permissive - Reactor Trip and Bypass Breaker Open
2: P-6 IR block permissive - 1x10^-10 amps (1 of 2)
3: P-7 at power permissive - P-10 > 10% (2 of 4) or P-13 >10% (1 of 2)
4: P-8 single loop loss of flow RX trip permissive - 50% (2 of 4)
5: P-9 Turbine Trip RX Trip Permissive - 45% (2 of 4)
6: P-10 IR and PR low setpoint RX Trip Block Permissive
- 10% PR (2 of 4)
7: P-11 MS/PZR SI permissive 1950# PZR press. (2 of 3)
8: P-12 LO LO T-ave 550F (2 of 4)
9: P-13 10% turbine power (1 of 2)
10: P-14 High High SG Level - 90.8 SG NR (2 of 4 any SG)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

List all Control Permissives

A

1: C-1 20% IR equiv. current (1 of 2)
2: C-2 103% PR (1of 4)
3: C-5 15% turbine power (1 of 1)
4: C-7A 15% or greater step change in turbine load or a >7.5%/min ramp decrease for 600 sec (1 of 1)
5: C-9 Condenser Available, >25” HgV (2 of 3) and at least 1 CW bkr shut
6: C-11 223 steps on Control Rod Bank D
7: C-16 Auctioneered low Tave <553 or Auctioneered low Tave 20F < Tref
8: C-20 AMSAC Control permissive - 20% turbine power (2 of 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Define P-4

A
Reactor trip permissive - Reactor Trip and Bypass Breaker Open
Dual Trained
Inputs to: 
- SI auto initiation block logic
- FWI circuitry
- Turbine Trip Circuitry
- Steam Dump Circuitry
- Limit MFP speed, limits to 4400 RPM
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Define P-6

A

IR Block Permissive - 1 x 10^-10 IR amps (1 of 2)

  • Allows blocking of the SR Trip (10^5 cps in SR)
  • Resets at 5 X 10^-11 amps decreasing (2 of2)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Define P-7

A
At Power Permissive 
- P-10 (RX Power) > 10% (2 of 4) or
- P-13 (turbine power) > 10% (1 of 2)
enables trips from:
- PRZ high level
- PRZ low level
- RCS two loop loss flow
- RCP undervoltage
- RCP underfrequency
Rests at 8% decreasing (3 of 4 RX power or 2 of 2 Turbine power)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Define P-8

A

Single Loop Loss of Flow Reactor trip Permissive
- 50% PR (2 of 4)
This permissive enables the RCS single loop loss of flow reactor trip
resets at 48% decreasing (3 of 4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Define P-9

A

Turbine Trip Reactor Trip Permissive

  • 45% PR (2 of 4)
  • resets at 43% decreasing (3 of 4)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Define P-10

A

IR and PR low Setpoint Reactor Trip Block Permissive
10% PR (2 of 4)
Performs the following:
- Allows manual block of the IR trip (25%) and rod block
- allows the operator to manually block the PR overpower low setpoint RX trip (25% PR)
- Provides a back-up signal to set the RPS source range block (P-6 back up)
- inputs to P-7
resets at 8% decreasing (3 of 4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Define P-11

A

MS/PZR/SI permissive - 1950# PZR press (2 of 3)
resets at 1941 decreasing (2 of 3)
- allows manual block of low PZR press. SI
- allows Manual block of Low steam line press. SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Define P-12

A

LO LO Tave - 550 Tave (2 of 4)
either train will block Steam Dumps
Resets at 551F increasing (3 of 4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Define P-13

A

10% turbine power (1 of 2)

  • inputs to P-7
  • resets at 8% decreasing (2 of 2)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Define P-14

A

HIGH HIGH SB Level - 90.8 SG NR (2 of 4 any SG)
-Trips turbine
-Trips both MFPs
-FWI
-Prevents starting of the SUFP
resets at 89.8 decreasing (3 of 4 on all SG)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Define C-1

A

20% IR equiv. Current (1 of 2)
- blocks all manual and auto rod withdrawal
resets are 10% IR equiv. current decreasing (2 of 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Define C-2

A

103% PR (1 of 4)

  • Blocks all manual and automatic rod withdrawal
  • 1 channel can be bypassed (coincidence is now 1 of 3)
  • resets at 101% (4 of 4)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Define C-5

A

15% Turbine power (1 of 1)

  • From PT-505, enables auto rod withdrawal above 15% turbine power
  • Resets at 13% and blocks auto rod withdrawal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Define C-7a

A

15% of greater step change in turbine load or a >7.5%/min ramp decrease for 600 seconds (1 of 1)

  • From PT-506, arms steam dump when in Tave mode
  • Manually reset by operator
17
Q

Define C-9

A

Condenser available

  • Better than 25” Hgv (2 of 3) and at least 1 CW Breaker shut.
  • Loss of signal will block Steam Dump Operation
18
Q

Define C-11

A

223 Steps on Control Rod Bank D

- Prevents auto rod withdrawal beyond 223 steps on control bank D

19
Q

Define C-16

A

This interlock blocks any further load set increase and therefore prevents any further opening of turbine control valves. Prevents additional loading of the turbine if either of following conditions are met:
- Auctioneered low Tave is <553F
OR
- Auctioneered low Tave is 20F less that Tref

20
Q

Define C-20

A

AMSAC Control Permissive - 20% turbine power (2 of 2)

  • Turbine First stage Pressure transmitters, PT-505 and 506 are inputs
  • low level setpoint is 13%
  • Trips turbine and actuates EFW, does not trip reactor.