Steam System. Flashcards
- What is dry steam?
Steam with moisture content of less than 2% is considered to be saturated steam.
- What is boiler trim?
Most of the devices connected to a boiler except the burners and their controls are considered boiler trim.
- List the various accessories known as boiler trim?
- Safety relief valves (pop safety).
- Water gage (sight glass).
- Pressure gage.
- Pipe siphon (pigtail).
- Pressure trolls.
- Low-water cutoff.
- Working range on the safety relief valve on a low-pressure steam boiler pops?
Opens when the pressure in side the boiler reaches 15 psig and closes when the pressure drops to 12 psig.
- Parts of water gage (sight glass)?
- 2 nipple and coupling connected to boiler.
- 2 gage cock.
- Sight glass.
- How steam gage should be graduated?
To at least 1-1/2 times the set pressure of the safety relief valve.
- What is compound gage?
It measures both positive and negative pressure. On the left side of the gage negative pressure is measured in the range of 0 to 30” of mercury )Hg), on the right side - positive pressure is recorded 0 to 30 psig.
- Parts of pipe siphon?
- Lower handle shutoff cock.
- Pig tale.
- Toe with inspector test gage connection.
- Gage.
- Two types of pressure trolls?
- Additive.
2. Subtructive.
- Two types of low-water cutoff?
- Float type.
2. Electric probe.
- What is pressure troll?
A mercury switch that turns the burners of the boiler off and on. Controls the operating pressure range of boiler.
- What is steam Header?
The horizontal piping connected to the boiler steam outlet or outlets.
- What is steam supply main?
The steam pipe which carried steam from the boiler to the heating units.
- What is Hardford loop?
Designed to protect boilers against the loss of water under conditions that would otherwise permit water flow out of the boiler into the return main.
- What is wet return?
Any return line which is located below the water level of the boiler. It is completely full of water and does not contain steam or air.
- What is dry return?
Any return line located above the boiler water line. A dry return can contain air, steam or condansate.
- What is equalizing line (Balance pipe)?
A pipe which connects the steam header to the boiler return connection. Drains the condensate from the steam Header and returns it to the boiler below the water line. Equalizes the supply pressure in the return line to boilers. This prevents the boiler water from flowing out of the boiler into the return mail.
- What is a drip connection?
A vertical pipe that connects the end of steam supply main and the wet return.
- What is dimension A?
The distance required between the bottom of the last steam cutting line and the boiler water line. Must be used in the gravity return systems in order to overcome the system pressure drop and return the condensate to the boiler.
- What is down feed?
A steam heating system or part of the system in which the heating units are located below the supply main.
- What are heating units?
In order to transfer the heat that is in the steam to the space to be heated. heat transfer units are required. Cast iron radiators, convectors and similar heat out put units are used.
- What are air vents?
Device that allow air to escape when steam begins to circulate. Air vents are heat activated valves that permit air to escape from a steam systems piping and radiators. They close when steam or water enters the vent and reopen when the boiler cycles off, and the temperature inside of the vent drops.
- Causes of water hammer in one-pipe system?
- Water packet or water trap.
2. Condensate produce water hammer.
- What is start up (piping and pick-up) load?
The condensate that”s formed in bringing the piping and radiators up to steam temperature
- What is priming?
It is the carrying of small particles of water into the steam piping.
- What is foaming?
A rapid fluctuation in boiler water level created by impurities on the surface of the water, causing an increase in surface tension of the boiler water.
- What does float or air vent contains?
A volatile liquid usually a mixture of alcohol and water.
- How does steam header and return are connected to boiler?
By swing joints.
- Why can not You reduce boiler outlet pipe size?
This will increase steam velocity that will lead to carry boiler water into steam piping. After that steam will be absorbed into the water causing the steam to condensate before it can reach the heating units.
- Why must You use both outlets of steam boiler?
If You cap one the steam velocity leaving the boiler will increase and the water will slant towards the uncapped outlet leaving the back section of the boiler exposed to the heat generated by the burner.
- What is NOWL?
The normal operating water line.
- How shall the supply rise into the steam header from boiler?
The bottom of the header mast be a minimum 24” above NOWL. That will keep the steam dry, most of the water droplets will fail back into boiler.
- How should the steam riser supplying steam to the system main be installed?
- Shall be after the boiler risers and before the equalizing line . If it will be installed between the boiler risers, the high velocity steam is entering the steam riser from two directions, the drops of water will have no chance to drop down and flow into equalizing line.
- How shall equalizing line be connected to boiler?
Equalizing line is usually smaller than the header and the elbow at the end of the steam main is pointed straight down.
- Location the main air vent/?
Near the end of dry return.
- What is dimension A for most system?
28”.
- Operating pressure of most one-pipe system?
2 psig.
- The operating pressure range of pressure troll for one-pipe system boiler?
1-1/2” - 2”.
- Two pressure settings for Air vent?
- Maximum pressure.
2. An operating pressure (drop-off pressure).
- Location Main vent?
- Tee for main vent 15”-18” from the end of the last steam carrying main.
- A 6”-10” long pipe nipple should be installed between the top of Tee and the main vent.
- How shall the steam supply main be itched away from the boiler?
At least 1” for each 20 feet.
- Minimum pitch on branch steam piping of one pipe system?
1/2” for 10’ of pipe distance.
- Two methods of connecting a branch to a steam main?
- Taken off the main at a 45* angle.
2. Taken off a 90*.
- How can You control the flow of steam into radiator of one-pipe system?
Radiator valves must be fully open or closet. To regulate the steam flow to radiator You shall regulate the rate at which air is eliminated.
- how can You evenly supply heat to all radiators in one-pipe system?
Air vents with the largest air venting capacity should be installed on the radiators furthest away. Contact air vent manufactures for air vent selection charts.
- What make condensate in gravity return steam system flow back into the boiler?
A drip dimension, which is often cooled the “A” - dimension.
- What is drip connection?
It is just a piece of pipe which is installed vertically at the end of the last steam carrying main.It is standard practice for a system designed for 1/2 psig pressure drop manage the minimum distance for dimension “A” not less than 28” above the boiler water line.
- Location Tee for Hartfort loop connection in equalizing line?
- Residential boiler - 2” below the water line of boiler.
2. 4” for commercial installations.
- They shall You use close nipple, when assembling a Hartford loop?
If You use longer nipple and the.water level in the boiler drops the nipple will fill with steam and when the condensate does return water hammer will occur.
- What is counter flow system?
The steam and condensate flow in opposite direction in the steam supply main.
- Size of sin steam pipe in a counter flow one-pipe system?
It is sized one size larger than other type of one-pipe steam heating system and pitched 1” for each 10’ of pipe distance.
- Difference between one- pipe counter flow system and parallel one?
- The main pitches upward away from the boiler twice as much as a parallel flow system.
- No return riser is used, no Hartford loop is needed since since the return is above the water line.
- The boiler header must enter the top of the main, unlike parallel flow systems, where the main feeds of the top of the boiler header.
- Dimension “A” is at the lowest point of the steam main, but doesn’t have to be 28” because is almost no pressure drop from the boiler to the point of condensate return. The only loss is the friction loss for the condensate.
- What is the maximum Header Length for one-pipe counter flow system?
100 feet.
- Where shall you install main vent for one-pipe parallel system?
At the top of each riser and at the end of the steam main.
- How shall You pitch down riser connection for one-pipe parallel up feed system?
Dripped riser pitch down from the main, I dropped riser connection pitch up ford from the main.
- Requirements of one-pipe parallel down feed system?
Express steam riser feeds top floor steam main. Steam main feeds steam to down feed risers and branches. Main and dripped risers insensate to returns.
- Where shall You provide the Main Vent For one-pipe parallel downfeed system?
At the top of each riser and just above the lowest branch on each of the down feed riser.
- Riser connection fittings for one-pipe parallel downfeed system Of the main?
Tee facing down at 45* engle, 45, 2 90 elbow swing.
- What shall You use instead bullhead tee when express riser feed on both sides?
Side outlet tee, long radius ell on the top, two 45* ell on the side.
- How does Steam Main offset abstractions?
- Install full size main on the top.
- Provide condensate piping below abstraction.
- Tee connected two loops together shall be installed with 1” offset following direction of flow.
- How shall You install dry return piping around abstraction?
- Make full size dry return below the abstraction. Provide Tee with clean out on the lowest end of the loop.
- Make 1” offset between upstream and downstream tee.
- Connect smaller loop above the abstraction for air movement.
- The limitation of one-pipe steam system?
- They are designed to operate at 2 psig.
- The normal pressure drop is 1/2 psig per 100’. The length of the steam main is limited to 400’.
- Radiator valves must be fully open or closed.
- The basic function of steam traps are?
- Prevent the loss of steam and maintain the pressure differential between the supply and return sides of a steam system.
- Allow the passage of condensate, air and other non-condensate gases from the steam supply to the condensate return portion of a steam system.