Stator & Isophase Bus Cooling (CE) Flashcards
What is the purpose of these systems?
Stator Cooling: To provide cooling for the main generator stator windings, generator bushings, the rectifier excitation system and the generator lower frame extension
Isophase Bus Cooling: provides cooling for the electrical buses from the main generator terminals to the main power transformer and the Unit Aux Transformer
What is the cooling medium for the stator cooling water heat exchangers?
TC
What system supplies makeup water to stator cooling system?
DW
What system provides cooling to the collector housing heat exchanger?
WC
What is the capacity of the Stator Cooling Water pumps? Power source?
100% capacity pumps each
NG
What would cause the standby Stator Cooling Water Pump to auto start?
In-service pump’s discharge pressure decreases below its low discharge set point
What is the capacity of each Stator cooling cooler?
80% capacity
What flows through the tubes of the cooler?
TC
Where is the Stator Cooling Storage Tank located?
140’ Turbine Building
What is the capacity of the tank?
1070 gallons
What is the purpose of the deionizer?
Maintain low electrical conductivity by continuous removal of dissolve mineral salts
How much of the Stator Cooling Water flow stream is directed through the deionizer?
~ 10%
Where are the two test pushbuttons for the auto start of the standby pump?
Locally and in the Control Room
While the plant is operating, the in-service discharge pressure drops low enough to start the standby pump. Pressure is returned to normal. What is the status of the standby pump?
Still running, it will need to be secured manually
Unless there’s a turbine trip of course
What pressure is the stator cooling water being supplied to the main generator maintained at?
60 psig (the valve is locked in this throttle position)