specific hazards working with transformers Flashcards
OSHA does not require a written job briefing if a worker is working alone.
true
The ? fuse reduces nuisance fuse blowing due to transients such as lighting.
t-link
Back-feed will only occur on a transformer if full secondary voltage is applied from X1 to X3.
false
A transformer tank may become energized on a single-bushing transformer if the tank is not grounded and a back-feed situation happens.
true
A current-limiting fuse in series with the cutout will ?
reduce the risk of violent transformer failure
The current available out of the primary bushings is always twice the secondary current.
false
Installing a transformer over a hot secondary with the leads installed ? .
should never be done
The primary voltage and the ? rating of the transformer are two factors that determine the fuse size.
kva
A company specifies the ? and ? of a fuse to be used in a transformer.
size / speed
When it blows open, the internal primary fuse of a CSP will deenergize everything above it to the main line.
false
It is not a recommended practice to use a CSP as part of a bank of transformers.
true
To energize a transformer, a load-break elbow on an underground transformer should be inserted by hand.
false
Paint discoloration on an overhead transformer may be a sign of ?
overheating
External damage to a transformer tank may include ?
damaged bushings, leaking oil, and bulged tank.