A load test taken with a clip-on ammeter and a multimeter will indicate if a transformer is overloaded at the time of the test.
true
Overload peaks of ? do not affect a transformer.
5 minutes
When a maximeter is clamped around an energized conductor, never ?
change taps on the meter
Maximeters record the ? during the time of the test.
highest load
The red indicator needle on a maximeter indicates the load at the time of the reading.
true
The tap setting on the side of the maximeter should be set to ? if placed on a 25-kVA single-phase transformer.
40/1
A single-phase transformer should have a maximeter placed on each secondary lead from the transformer.
true
Total phase current times line to neutral voltage equals kilovolt-ampere.
false
A 15-kVA single-phase distribution transformer shows 75 amperes on X1 and 60 amperes on X3. Voltage is 120 volts from each secondary bushing to the neutral. The transformer has exactly ? of load.
16.2 kva
A balanced load on a transformer is when ?
both phase to neutral leads have the same load.
Since a single-phase distribution transformer has two secondary coils, it is possible for only one coil to be overloaded.
true
A 15-kilovolt-ampere transformer is checked and is carrying 19.5 kilovolt-amperes; it should be reported as overloaded.