Sprinklers are listed to achieve what
-Fire control (standard spray & extended coverage)
-Early fire suppression (ESFR)
-Life Safety (residential)
What is the main objective of most sprinklers
Fire control
Hose stream allowance and time duration light hazard
100gpm & 30 minutes
Hose stream allowance and time duration ordinary hazard
250gpm - 60 or 90 minutes
Hose stream allowance and time duration extra hazard
500gpm & 90 or 120 minutes
Standard spray sprinklers can’t be less then ____ apart
6 feet
Bigger K factor means what for water pressure
Less pressure required
K factor Triangle
Q
_______
K | P(square root)
3 main types of obstructions are
- To sprinkler discharge
- To spray pattern development
- That prevent sprinkler discharge from reaching hazard
Standard spray upright and pendant from unobstructed ceiling
1-12”
Standard spray upright in obstructed construction
1-6” below beam, 22” max from deck
Fast response sprinklers RTI
<50 (less then)
Standard spray sprinklers RTI
> 80 (more then)
Any sprinkler between 50-80 RTI are considered what
Special response
what does a lower RTI mean
Higher the sprinkler operates - faster response
What does a higher RTI mean
Lower the sprinkler operates - slower response
Standard spray upright/pendant max coverage and distance (Light Hazard)
225sqft - 15ft
Standard spray upright/pendant max coverage and distance (Ordinary Hazard)
130sqft - 15ft
Standard spray upright/pendant max coverage and distance (Extra Hazard)
100sqft - 12 feet
Standard spray upright/pendant distance from wall
4”
Standard spray upright/pedant clearance from storage
18”
What do baffles permit when installed
Less then minimum spacing
Baffles are extended _____ above deflectors of uprights
2-3”
Baffles are extended ______ with deflectors of pendants
At least even with deflector
Baffles must be ____ wide
6”
Baffles must be _______ long
8”
Baffles can be used in what hazard classifications
All of them
What standard spray sprinkler (upright & pendant) cannot be used in extra hazard
Quick Response
Standard spray sidewalls throw water
Horizontally and down
Standard spray sidewalls light hazard coverage area and distance max
196sqft - 14 feet
Standard spray sidewalls in ordinary hazard max coverage area and distance max
100sqft - 10ft
Standard spray sidewalls minimum distance between heads (light & ordinary)
6 feet
Standard spray sidewall in light and ordinary hazard distance from wall
4” end wall
4-6 mounted
Standard spray sidewall in light hazard distance below ceilings unobstructed
Non/limited combustion
Standard spray sidewall in ordinary hazard distance below ceilings obstructed
12-18”
Standard spray sidewall max distance below storage
18”
Max coverage area for extended coverage sprinklers
20’ x 20’ (400sqft)
Min distance between extended coverage sprinklers (upright and pendant)
8 feet
Obstruction rule for extended coverage sprinklers
4 x rule along walls
4 x rule for joisting
Extended coverage sprinklers max coverage and spacing (light & ordinary)
400 sqft - 20 feet
Extended coverage sprinklers max coverage and spacing (Extra & High piled)
196sqft - 14’
Extended coverage sprinklers
-min from wall
-distance below ceilings
-distance below obstructions
-clearance to storage
Same as standard spray upright & pendants
Extended coverage sidewalls max coverage (light & ordinary)
400sqft
Extended coverage sidewalls max spacing (light hazard)
28 feet
Extended coverage sidewalls max spacing (ordinary hazard)
24 feet
Extended coverage sidewalls min distance apart
Shall not be within the protection area of another sprinkler without baffles
Extended coverage SW distance below ceilings obstructed
Light - non/limited combustion
Ordinary - 12”-18”
Extended coverage sidewalls distance of clearance to storage (light and ordinary)
18”
CMSA stands for
Control mode special application sprinkler
CMSA sprinkles produce what kind of water droplets
Large
CMSA minimum coverage area is
80sqft
CMSA heads in storage occupies, what heads are permitted on wet systems
Ordinary
Intermediate
High temp
CMSA heads in storage occupies, what heads are permitted on dry systems
High temp only
CMSA uprights can be attached to sprinkler piping what size
4” and less
If CMSA uprights are attached to sprinkler piping 4” or more what must be done
Heads offset 12” horizontally or vertically
CMSA sprinklers clearance to storage
36”
CMSA sprinklers coverage for
-N/C unobstructed and obstructed
- combustible unobstructed
130sqft
CMSA coverage for
Combustible obstructed
Racks combustible & obstructed
Racks N/C & unobstructed
100sqft
CMSA sprinklers max and min distance between
-N/C unobstructed and obstructed
- combustible unobstructed
12’ max
8’ min
CMSA min and max spacing
Combustible obstructed
Racks combustible & obstructed
Racks N/C & unobstructed
10’ max
8’ min
ALL uprights and pendants minimum from walls is
4”
CMSA sprinklers distance below unobstructed and obstructed ceilings
Unobstructed - 6-8”
Obstructed - 6-12”
CMSA - obstruction to spray pattern rule
3x the longest dimension away
24”
Obstruction preventing discharge from reaching hazard CMSA rules
- ## obstructions over 24” require coverage
ESFR stands for
Early suppression fast response
Early fire suppression requires
Fast operation to deliver a large volume of water using large water droplets with a central stream to penetrate the seat of the fire
RTI means
Response time Index
RDD means
Required delivery density
ADD means
Actual delivered density
When actual delivered density is less then required delivered density what happens
Sprinkler discharge is no longer effective enough to achieve early suppression
ESFR minimum coverage area is
64sqft
ESFR max area coverage is
100sqft
ESFR clearance from storage is
36”
ESFR shift rule is
1’ movement from max coverage area to eliminate obstruction issues
Spacing can never exceed 12’
What system are ESFR heads used on
Wet system
Flat ceiling is considered
2” up for every 12” out of
Draft curtains are to be a minimum of
24”
Draft curtains are used with what heads
ESFR
Fans have a max blade size of
24 ft
ESFR heads must be how far from fan
36”
ESFR sprinkler spacing storage less then <30
12ft
ESFR sprinkler spacing storage more then >30
10ft
Minimum distance between all special application sprinklers (CMSA, Residential, Extended, ESFR) (pendants and uprights)
8 ft
ESFR K- factor used in Non-combustible, Unobstructed + distance below ceiling
K 14
Upright - 3-12”
Pendant - 6 - 14”
ESFR K- factor used in Non-combustible, Obstructed + distance below ceiling
K 16.8
Upright - 3 to 12”
Pendant - 6 to 14”
ESFR K- factor used in combustible, Unobstructed + distance below ceiling
K 22.4
Pendant - 6 to 18”
ESFR K- factor used in combustible, obstructed + distance below ceiling
K 25.2
Pendant 6 -18 “
ESFR and CMSA heads clearance to storage
36”
ALL heads must be a minimum of what from a wall
4”
ESFR obstruction rules
Beam 12” or less - 12” away
>12” to 24 - 24” away
>24” - head on each side
Quick response early suppression sprinklers have an rti of
50 or less
Do not exist
Life safety sprinklers create a livable space how far above the floor
5 ft
Residential sprinklers must be
QR type
RTI of 50 or less
Listed for use in dwelling units
Wet system only
Residential sprinklers max coverage area is
Based off manufactures listing
Minimum distance between residential sprinklers is
8ft
Residential pendant or upright distance from ceiling is
1-4”
Residential SW from ceiling is
4-6”
Obstruction rule for residential
4 x Rule with a max of 36” for truss
Minimum of clear space to obstruction for residential SW is
8 ft
Shadow areas in residential cannot exceed
15sqft per head
Max width of residential shadow cannot exceed
24”
What do draft curtains do
Protect 2 different kinds of heads from cold solder where you can’t have a wall
What do draft stops do
Prevents heat from rising vertically
Dry sprinklers are to be installed
In areas with temps below 4C
Into the RUN of a Tee
If Mullions are more then ____ thick you need window sprinklers on each side
2”
In rack sprinklers require at least ___ for heights up to 30 ft
15psi
In rack sprinklers require at least ___ for heights over 30 ft
30psi
In rack K factor heads
5.6
8.0
11.2
In rack sprinkler heads are permitted to be less then ____ apart
6 ft
Max size of in rack system
40 000 sqft
Horizontal spacing of in rack shall not exceed
8 ft
Corridor sprinklers are listed for spacing of
28x12
28x14
Sprinklers installed where for combustible stairways
Top, Landings, below lowest landing
Non combustible stairs head location
Top and bottom, under first landing unless sealed off
Draft stop minimum depth
18”
Heads off draft stops
6-12”
Vertical opening head spacing
6’ apart
Large vertical openings are considered to be
1000sqft or greater
Horizontal dimensions greater then 20ft
What is installed at the bottom of an elevator shaft and at what depth
Sidewall sprinkler and 2ft above the floor of the pit
What is installed at the top of an elevator shaft
Upright, pendant (ordinary or intermediate)
Garbage chute sprinkler location
Top and bottom
Alternate floors
Chute terminal room
Sprinklers in duct work location
Top of vertical riser
10’ on centre, 5’ from duct entrance
Open grid ceiling rules
-1/4” min size grid
-Thickness can’t be more then open
-Opening must make up 70% of the area of ceiling
-Light hazard only
Cloud ceiling max ceiling height
20 ft
Max Ceiling gap is calculated how in cloud ceilings
1” gap per 1’ of ceiling height
Formula to omit sprinklers above cloud ceilings is
X=A/B
A= inches in gap between clouds
B= Ceiling height
X=Max inches of gap