SOP-03 - Loss of AC Power Flashcards
What are the entry conditions of SOP-01?
AC power is lost to one OR more of the following, with OR without loss of Emergency Diesel Generators:
2ENS*SWG101
2ENS*SWG102
2ENS*SWG103
2NPS-SWG001
2NPS-SWG003
2RTX-XSR1A
2RTX-XSR1B
2ABS-X1
2NNS-SWG014
2NNS-SWG015
RHR A is running in Suppression Pool Cooling when a loss of Line 5 occurs. What actions are required?
The plant is at rated conditions…
- You have just had a loss of both line 5 and 6
- Both Div 1 and Div 2 EDGs failed to start
- Div 3 EDG has started and energized its bus
What actions are required per SOP-03?
What is a sequential loss of power?
A loss of Line 6 occurs and Div 2 EDG fails to start. What actions are required?
What is used to determine if you are allowed to manually start and load Div 1 or 2 EDG per SOP-03?
Per Detail AA, verify none of the GREEN Annunciators are in.
What actions are required if a loss of Div 1 or 2 occurs and power can NOT be restored?
A loss of line 5 has occured, the Div 1 EDG starts and loads to the bus, the non-essentials are currently stroking closed. What actions are directed to restore the non-essentials iaw SOP-03?
A loss of line 5, then line 6 occurs, All EDGs energize their bus. What actions are required?
- Verify Non-essentials/MOV-50’s Isolate(Only one division’s valves req’d to close)
- 1 SWP Pump in each division starts
- Cooling flow to EDGs over 800gpm
Then
- Open the MOV-50’s
- Start avialable Low Press ECCS
- Start a second SWP Pump in each division
- Open Non-Essentials