SHORT CIRCUIT STUDY 2 Flashcards
when will be the stability of system will be lower?
when we have higher impedance
what are the inputs of grid we must get from client or utility?
1) 8 info(max and min 3ph Isc and corresponding X/R(4),max and min 1ph Isc and corresponding X/R(4))
with considered C factor
or
2)12 INFO(max sc current’s +ve,-ve,zero seq impedance and correspondin X/R(6) and min sc current’s +ve,-ve,zero seq impedance and correspondin X/R(6))
when will be +ve and -ve sequence will not be equal
if rotating machines are present near
sc mva formula
1.732open circuit voltage(V)sc current
3ph fault current will be higher or lower than SLG fault current generally
higher except in few cases
where SLG fault current will be more than 3 ph fault current?
1) solidly grounded gen(Z0 and Z2 less than Z1 for larger capacity)
2) solidly grounded wye side of a delta wye trafo of the 3phase core(three leg design)with no load
3) the ground wye side of auto transformer with tertiary delta
4) in delta/wye trafo, if there is no fault contribution from lv side
does SLG fault is affected by winding configuration?
yes
role of Isc/iL?
1) dictates what is the voltage drop in normal condition
2) dictates what is the voltage drop in motor starting
3) )dictates what is the THD in harmonics
4) dictates what is the system strength
5) dictates what is the fluctuation for oscillation(transient stability)
6) dictates what is the voltage for faults at other places
when sc current is more,how will be the voltage change?
less
in between peak value and RMS value, X/R and Z decides which one?
1) X/R decides peak value(higher X/R ,higher peak current)
2) Z decides RMS value
what decides what is the current for L-L fault?
+ve and -ve seq impedance
does NGR limits 3 phase fault current
no.it will limit SLG fault only
can we ask higher Xd” from gen manufacturer ?why?
yes because we can reduce fault current by means of higher impedance
in which system X/R value is higher ?
in HV .MV and LV has lower X/R
my X/R at different level?
1) X/R up to 60 when your system is close to trafo
2) X/R is 20 for long TL with high conductor size
3) X/R is 5 or 10 for long TL with small conductor size
4) X/R is small for distribution system