After taking to start, when does a Cooling Tower Pump Start?
Condenser Inlet opens to 33%, then pump starts. Discharge valves open to:
P-39A - 43%
P-39B - 39%
After taking to Stop, when does a Cooling Tower Pump stop?
Pump discharge valve starts to close.
At 33% open, pump will trip off.
Valve continues to close.
Cooling Tower Pump start permissives?
Condenser inlet water box full. Pump Trips Clear Emergency Stop pushbutton not pushed. Lubrication water flow > 8 gpm. Water box inlet valve closed. Cooling Tower pump discharge valve closed
EK 3501/3502, Clg Twr Pump P-39A (B) Hi Temp or Overload setpoints?
167F for bearing
266F for stator
EK-3508, Cooling Tower Pump P 39A Lube Low Flow and EK-3509, Cooling Tower Pump P-39B Lube Low Flow setpoints?
18 GPM
EK-3530, Makeup Basin Low Level setpoint?
P-39A Basin: 54%
P-39B Basin: 56%
Cooling Tower Pump trips?
Overcurrent
Ground Current
Differential Current
Bus Undervoltage
Dilution water pump trips?
Undervoltage
Overcurrent
SIAS Load Shed
MO-5313, MO-5314, P-40 Discharge to Cooling Tower overload setpoint?
Times out at 116 seconds.
Full stroke should be 60 seconds.
MO-5315, MO-5316, Cooling Tower Fill overload setpoint?
Times out at 116 seconds.
Full stroke should be 60 seconds.
Cooling Tower Fan Trips?
1) Turbine trip
2) High vibration (local reset)
3) Deluge activation (drain piping) - B onlye
4) Overload (local reset on breaker)
CTCS Master Start Fan Control defeats what?
While starting via the Master switch, fans will not trip on main turbine trip.
CTCS Init Reset will do what?
Its a warm reboot. Takes around 2 minutes.
Resets PPC alarms
Lamp Test of CTCS
Re-establishes communication with Cooling Towers
EK-3330 Cooling Tower E-30B alarm setpoint?
15 psig N2, indicates deluge actuation and fire.
EK-3333 (EK-3334) ‘A’ (‘B’) Cooling Twr Basin Level High/Low setpoints?
‘A’ Cooling Tower: high @ 611.17 ft and low @ 609.8 ft
‘B’ Cooling Tower: high @ 610.17 ft and low @ 608.8 ft)