An enable solenoid is located where?
On the 3 way ( scada 3 way) shuttle
An ENABLE solenoid is typically ____________ solenoid.
Normally Closed/ powered open
In event of outage, solenoid closes flow from 3 way, allowing 3 way to shift to hydraulic. (Therefore, if it is scada mode, solenoid will almost )
A pump lockout solenoid is found where?
On the downstream side of bypass reg (next to CRD)
A pump lockout is typically _________ / _________
A normally open/p.c. solenoid
( would be n.c./p.o. If on three way)
When the pumps are running, the pump lockout ( on the bypass) is in what position ?
Powered/energized CLOSED
so bypass will not open
A pump lockout comes (before/after) the CRD?
BEFORE. The bypass always works off the pilot, so energizing closed, your taking away the pilot control
What position is pump lockout (on bypass) when pumps are off?
Pump lockout (normally open/pc)
When pumps are off, pump lockout is de-energized, so it will be open)
The enable solenoid is _________ when the pumps are running?
The enable solenoid is de-energized(closed) when the pumps are running and the scada reg is on the hydraulic side.