Prevents A-Oxy Reactor and both hydrogen feed systems from operating when there is a communications failure between the CPU and the outside controllers.
FCS302 (Field Control Station-302) FAILURE
Prevents B & C-Oxy Reactors from operating when there is a communications failure between the CPU and the outside controllers.
FCS303 (Field Control Station-303) FAILURE
Shutdown A/B/C-Oxy reactor by isolating the feeds. The Recycle Gas Compressor will remain in operation to keep the catalyst bed fluidized.
200-A/B/C OXY SHUTDOWN SWITCH
Prevents catalyst from plugging cups and damaging feed distribution system when a Recycle Gas Compressor trips. Slumping of the catalyst bed can cause distributor plate and sparger damage during a Recycle Gas Compressor trip.
RECYCLE GAS COMPRESSOR (MCM-201 or 202 or 203) STOP:
Interlock is hardwired and activated when the compressors are stopped.
Prevents catalyst from plugging cups and damaging feed distribution system when a Recycle Gas Compressor trips. Slumping of the catalyst bed can cause distributor plate and sparger damage during a Recycle Gas Compressor trip.
RECYCLE GAS COMPRESSOR (MCM-201 or 202 or 203) STOP:
Interlock is hardwired and activated when the compressors are stopped.
Prevents the Oxy Reactor from operating with an Oxygen enriched atmosphere. Interlock is DCS activated when 2 of 3 Oxygen analyzers indicate 7 % Oxygen in the Recycle Gas stream
RECYCLE GAS HHH OXYGEN ANALYZER (A24 A/B/C-1/2/3):
Prevents the Reactor from operating with an Oxygen enriched atmosphere. Interlock is DCS activated when 2 of 3 Oxygen analyzers indicate 10% Oxygen in the Recycle Gas stream.
RECYCLE GAS HHHH OXYGEN (A24 A/B/C-1/2/3)
Interlock is DCS activated when HCI flow is less than 1400 scfm for greater than five seconds. Prevents Reactor Startup when the HCl flow may be too low to prevent uncontrolled Ethylene, Oxygen reaction within the Reactor.
HCl LLLL FLOW (F201 A/B/C AND F201 A/B/C-1)
Interlock is DCS activated when HCI flow is less than 2100 sofm for greater than five seconds. Prevents Reactor from operating when the HCI flow is less than intended design.
HI LLL FLOW (F201 A/B/C AND F201 A/B/C-1)
Interlock is DCS activated when the Ethylene flow is less than 950 scfm for greater than five seconds. Prevents Reactor from operating with excessive HCI resulting in inefficient
Reactor operations due to loss of catalyst fluidization.
ETHYLENE LLL FLOW (F202 A/B/C)
Interlock is DCS activated when the Oxygen flow is less than 480 scfm for greater than five seconds. Prevents Reactor from operating with excessive HCI resulting in inefficient
Reactor operations due to loss of catalyst fluidization.
OXYGEN LLL FLOW F204 A/B)
Interlock is
DCS activated when Recycle Gas becomes less than 4000 scfm for greater than five seconds. Prevents the Reactor from operating with insufficient catalyst bed fluidization resulting in possible catalyst plugging of cups and damaging of feed distribution system. Slumping of the catalyst bed can cause distributor plate and sparger damage during a Recycle Gas Compressor trip.
RECYCLE GAS LLL FLOW F206 A/B/C AND F206 A/B/C-1)
Interlock is DCS activated when level reaches 20 %. Prevents liquid carryover to the Recycle Gas Compressors (MCM-201/202/203). Compressors are designed to compress gas, not liquid. Liquid entering the compressor can cause severe damage.
MTK-211 or 212 or 213 HHH LEVEL (L273A or L273B or L273C
Interlock is DCS activated when Ethylene supply pressure increases to 150 psig. Prevents Reactor from operating with excessive Ethylene concentration resulting in a fuel rich atmosphere
ETHYLENE HEADER HHH PRESSURE (P202)
Interlock is DCS activated when Ethylene supply pressure reaches 150 pig. Prevents Reactor from operating with excessive Ethylene concentration resulting in a fuel rich atmosphere
ETHYLENE HEADER HHH PRESSURE (P220)