Feed Controllers Flashcards

1
Q

Measures HCL flow through PCV-200/270 to MTK-695.

A

F200/270

HCl vent to MTK-695

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Regulates HCl feed flow to reactor.

A

F201 A/B/C

Oxy HCl flow controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Regulates F201 A/B/C to control the total sum of HCl feed F201 A/B/C and HAPF Unit HCL F514

A

F201 A/B/C-S

Oxy Total HCl Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Regulates main ethylene flow to reactor. Normally set in ratio to HCl feed flow, to maintain feed stoichiometry, and control excess ethylene in recycle gas.

A

F202 A/B/C

Oxy Main Ethylene Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Regulates trim ethylene flow. Normally a fixed flow approx 500 scfm to give main feed valve room to control.

A

F203 A/B/C

Oxy Trim Ethylene Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Regulates main O2 feed to reactor. Normally set in ratio to HCl flow to maintain feed stoichiometry and control excess O2 in recycle gas.

A

F204 A/B/C

Oxy Main O2 Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Regulates O2 trim feed flow to reactor. Usually with a set flow of 300 scfms to give main feed valve room to operate.

A

F205 A/B/C

Oxy O2 Trim Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Regulates recycle gas flow to reactor. Normally runs 10,000-15,000 scfm to control superficial velocity depending on rates.

A

F206 A/B/C

Oxy Recycle Gas Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Regulates H2 flow to hydrogenator.

A

F207/F280

Hydrogen Flow Controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Regulates purge nitrogen flow during recycle gas compressor trip. Normally throttled in field to approx 1600 scfm.

A

F209 A/B/C

Purge Nitrogen for grid plate and associated equipment protection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Prevents over pressure of HCl header, by venting to MTK-695.

A

P200/270

HCl header pressure controller.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Regulates Oxy HCl feed pressure approx 85 psi to aid in accurate feed flow.

A

P201/P275

Oxy HCl feed pressure controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Regulates ethylene feed pressure, approx 85 psi to in accurate feed flow.

A

P202/P220

Oxy ethylene feed pressure controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Indicates recycle gas comp discharge pressure.

A

P204 A/B/C

Oxy O2 feed pressure controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Indicates Oxy H2 feed pressure

A

P207/280

MRE-201/202 Feed H2 pressure transmitter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Indicates Oxy HCl supply temperature.

A

T200

HCL header temperature transmitter

17
Q

Indicates HCl feed temperature after leaving hydrogenator.

A

T201/T277

Reactor HCl feed temperature transmitter

18
Q

Regulates ethylene feed temperature by adjusting steam flow to preheater. Temperature is set to prevent dew point corrosion and aid in accurate feed flow reading.

A

T202/T220

Oxy Ethylene Feed Temperature Controller

19
Q

Regulates O2 feed temperature at approx 156 C. Temperature is set to prevent dew point corrosion and aid in accurate feed flow reading.

A

T203/T230

Oxy O2 Feed Temperature Controller

20
Q

Indicates recycle gas compressor discharge temperature.

A

T204 A/B/C

RG comp discharge TT

21
Q

Regulates recycle gas feed temperature to approx 177 C.

A

T205 A/B/C

Oxy recycle gas temperature controller

22
Q

Indicates Oxy MRE-203/204 H2 feed temperature.

A

T206

MRE-201 H2 feed TT

23
Q

Indicates Oxy H2 feed pressure.

A

P207/P280

MRE-201/202 H2 feed PT

24
Q

Indicates Oxy HCl supply temperature.

A

T200

HCl supply TT

25
Q

Regulates HCl feed temperature to prevent dew point corrosion and aid in acetylene conversion.

A

T207/T275

Reactor HCl feed temperature controller

26
Q

Regulates ethylene feed temperature by adjusting steam flow to preheater. Temperature is set to prevent dew point corrosion and aid in accurate feed flow reading.

A

T202/T220

Oxy ethylene feed temperature controller

27
Q

Regulates hydrogenator MRE-201 HCL feed temperature.

A

T207

Hydrogenator MRE-201 feed temperature controller

28
Q

Indicates hydrogenator bed temperature in MRE-201.

A

T208

MRE-201 TT

29
Q

Regulates hydrogenator MRE-202 HCl feed temperature.

A

T275

Hydrogenator MRE-202 feed temperature controller

30
Q

Indicates hydrogenator MRE-202 bed temperature.

A

T276

MRE-202 temperature transmitter

31
Q

Indicates Oxy MRE-205 H2 feed temperature.

A

T280

MRE-202 H2 feed TT