Safeguards Flashcards

1
Q

What are the unlatched actions of a Safeguards actuation?

A

Rx Trip

Containment Isolation

MFW Isolation

CCS Containment Isolation (V200/V207/V208)

CVS Makeup Isolation (V90/V091) w/ PZR Level High-1 (23 % (2/4))

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the latched actions of a Safeguards actuation?

A

RNS Containment Isolation

CMT Actuation

Enables CSF visual alerts

  • Note:*
  • CSF - Critical Safety Function (Display on Ovation)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the primary function of the safeguards actuation signal?

A

CMT Actuation

Ensures coverage of active fuel for:

  • Heat removal
  • Clad integrity
  • Peak clad temperature < 2200 °F

Boration (Keff < 1.0)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How long must the operator wait to Reset/Block Safeguards on the PDSP?

A

60 Seconds w/ P-3

After 60 seconds following safeguards with P-3 the Reset/Block soft control on the PDSP resets/Blocks ALL safeguards initiation signals. The operator can still manually initiate safeguards.

P-3 /// Rx Trip breakers open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will initiate Safeguards?

A

Containment Pressure - High 2 [6.2 psig (2/4)]

PZR Pressure - Low 3 [1815 psig (2/4)]

SL Pressure - Low 2 [560.3 psig (2/4 on 1/2)]

RCS TCold - Low 2 [505 °F (2/4 on 1/2)]

Manual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How can you manually initiate Safeguards?

A

2 PDSP switches (1/2)

1 RSR switch (1/1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

For the Containment Pressure - High 2 Safeguards Actuation Signal, what is the set point and coincidence?

A

6.2 psig (2/4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

For the PZR Pressure - Low 3 Safeguards Actuation Signal, what is the set point and coincidence?

A

1815 psig (2/4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

For the SL Pressure Low-2 Safeguards Actuation Signal, what is the set point and coincidence?

A

560.3 psig (2/4 on 1/2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

For the RCS TCold - Low 2 Safeguards Actuation Signal, what is the set point and coincidence?

A

505 °F (2/4 on 1/2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which Safeguards signal provide protection < P-11 (PZR Pressure ≤ 1970 psig)?

A

Containment Pressure - High 2 [6.2 psig (2/4)]

  • Note:*
  • All other signals Manual Block ≤ P-11 / Auto Unblock > P-11*
    • *

P-11 /// Divisional PZR Pressure ≤ 1970 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly