RPS Flashcards
What are the power supplies for RPS channels and what happens on a loss of power to channel?
RS-1/2/3/4 supply channels A - D respectively.
A loss of power to channel will trip associated channel. If loss of power to 2+ channels, reactor will trip.
What NI and NNI instruments supply RPS?
NI - Rx Power from NI-5/6/7/8, Rate of change of rx power (SUR), Imbalance
NNI - Thot, RCS pressure, RCS flow, RX bldg pressure, RCP status, MFP status, Turbine status
What is the RPS trip logic? What if channel is bypassed?
2 out of 4 channel trips will trip the reactor and open all CRD breakers (AC, DC, and Electronic).
If channel is bypassed, then changes to 2 of 3 logic.
What is purpose of SD Bypass and what trips are in place when it is initiated?
SD Bypass bypasses the low RCS pressure and RCP status trips to allow CRD positioning and testing at low RCS pressures or when RCPs off.
High RCS pressure trip (1720#)
High power trip (5%)
What initiates power/pump trip?
- One pump per loop and RX power >/= 55%
- No pumps in a loop and power > 0%
Underpower relay will drop out when power is 25 to 50% of full load (sheared shaft) or pump breaker open.
What are the automatic and manual RPS trips?
What are the design criteria for RPS?
Single Failure - No single failure will prevent a protection system from fulfilling its protective functions or initiate unnecessary protective action.
Redundancy - All protection channels are implemented by redundant sensors, measuring channels, logic and actuation devices.
Independence - Electrically independent
Separation - RPS channels are physically separated and electrically isolated from other instrumentation.
Manual Trip - Manual trip switches independent of auto trips.
Manual Testing - Test methods
Environment - Environmentally qualified
Seismic
Loss of Power - Loss of power will result in channel trip.
Module Removal - Removal of module will cause channel trip.
What is the purpose of the buffer amplifier?
Provide electrical independence and separation for analog signal. Faults outside of RPS cabinets are not reflected into channel.
What is purpose of bistable?
Converts analog to digital output when setpoint is reached.
What is purpose of contact buffer?
Communicate status of remote equipment or instrumentation to RPS and provide electrical isolation for digital signals originating outside the system.
How is power and imbalance signal generated?
linear amplifier signals from top and bottom detector are sent to summer/difference module. They are summed for total power reading and difference for imbalance.
How is RCP status obtained in RPS?
Contact monitors are used to monitor RCP status and input into power to pumps and high power trip setpoint based on pump configuration.
What is the purpose of high power/imbalance/flow?
Trips when power is too high for associated RCS flow. RCP status plays in to this trip due to lowering flow. If at 100% and RCP trip, RX will trip due to this protection.
What is the purpose of the RX Trip Module?
Provides light indication of channels tripped. Provides manual bypass function and performs channel and system functions.
Describe how Rx Trip Module provides a trip signal.
RTM provides the interfac between RPS and trip devices in the control rod drive system.
A trip de-energizes the K relay opens associated contact which ultimately opens the K contacts in the UV string.