Refrigeration System Operation Flashcards

1
Q

Double suction riser are used in refrigeration system when

A

large fluctuations in system capacity will occur

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Suction risers are typically reduced by one size over that of the main suction run

A

to increase refrigerant velocity to aid in proper oil return

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When soldering a copper pipe connection which of the following processes allow for alloy to be draw into the space between copper pipe and the fitting connection?

A

capillary action

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Before proceeding to make any braze connection in a refrigeration system all of the internal piping should be purged of atmosphere with

A

CO² or nitrogen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The liquid receiver is located between the?

A

condenser and the expansion device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which device is used in a refrigeration system to protect the compressor from liquid slugs?

A

suction accumulator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which device is used to stop the flow of liquid or vapor in a refrigeration system?

A

solenoid valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Why is it important to know the direction that a scroll compressor is rotating?

A

it will only pump refrigeration in one direction of rotation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

An electric motor that has a voltage rating of 120 volts will have an upper and lower allowable voltage limit of

A

108 to 132 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The flapper valve design is less efficient than the discus valve design because

A

the cylinder has more clearance volume than the discus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Liquid refrigerant entering the compressor is potentially more damaging for this type of compressor over the others listed

A

reciprocating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Discus, ring, and flapper valves are not used on

A

screw compressors & scroll compressors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The main function of a condenser in a refrigeration system is?

A

reject the heat that is absorbed in the evaporator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The shell and tube condenser is a type of

A

water cooled condenser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

One of the main disadvantages of a water-cooled condenser is that mineral deposits can build up acting as a/an

A

insulator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A flow regulating valve could be used on this type of condenser

A

shell and tube & tube in tube

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

On a water cooled condenser the water leaving the condenser is normally ______ lower than the condensing temperature of the unit

A

10º F

18
Q

On a standard efficiency air-cooled condenser the ambient air entering the condenser will be approximately ________ lower than the condensing
temperature if the unit is under normal load and properly charged

A

30º F

19
Q

A head pressure control system would be used on this type of application

A

unit located in a colder climate operating all year

20
Q

What type of expansion valve regulates its flow based from suction line superheat?

A

TXV

21
Q

Systems where the pressure drop across the evaporator is excessive would typically use a/an.

A

externally equalized TXV

22
Q

On a system equipped with a TXV, when the load on an evaporator decreases.

A

the TXV decreases the flow of refrigerant

23
Q

When referring to a power head on an expansion device the bulb is

A

normally charged with a fluid similar to that of the system refrigerant

24
Q

By subtracting the low side evaporator outlet temperature from the low side saturation temperature the technician would be calculating?

A

evaporator superheat

25
Q

On a typically evaporator employing a TXV the liquid refrigerant should be completely boiled to a vapor?

A

near the evaporator outlet

26
Q

What type of TXV would be best for an application that was exposed to fluctuating ambient temperatures?

A

balanced port TXVs

27
Q

Pressure-limiting TXV’s are generally applied on systems when

A

it is necessary to shut off the refrigerant flow to the evaporator when the suction pressure reaches a predetermined pressure

28
Q

Which of the following is not true regarding the evaporator in a refrigeration system?

A

it rejects heat from the conditioned space

29
Q

Heat that is added to the refrigerant stream after the 100% saturated vapor point is called?

A

superheat

30
Q

Multiple refrigerant circuits are preferred on evaporators that are?

A

large or long

31
Q

In a system where the evaporator temperature operators above 32º F the technician needs to be concerned with?

A

none of the above

32
Q

The fin spacing per inch on a medium-temperature evaporator is

A

closer together than on low-temperature evaporator

33
Q

A refrigeration system that utilizes two or three stages of low temperature refrigeration

A

is called a cascade refrigeration system

34
Q

When leak testing a refrigeration system using a high pressure nitrogen tank the technician should always

A

use a pressure regulator and safety relief value at the nitrogen tank

35
Q

The maximum pressure that can be applied to a refrigeration system when pressure testing is

A

determined by the systems rated nameplate test pressures

36
Q

The safest way to charge refrigerant into a system that is running is with

A

vapor into the low side

37
Q

When heating a refrigerant cylinder the technician should never use

A

any type of open flame

38
Q

Refrigeration systems must be fully evacuated before charging with refrigerant

A

to remove air and moisture from the system

39
Q

A vacuum pump will lose its ability to draw a deep vacuum over time because

A

the oil becomes full of moisture and acids which will decrease the capability of the vacuum pump

40
Q

A refrigerant service valve must be placed in the

A

mid position in order for the technician to access the system

41
Q

When using a micron gauge to measure vacuum the system should be evacuated to a level of _____ to ensure that non condensables and moisture have been adequately removed

A

500 microns