Rack Systems Flashcards
Large or small compressors on parallel compressor racks, which are usually dedicated to the coldest cases, are called?
satellite compressors
and
booster compressors
What is a true statement regarding the operation of a parallel rack system?
A. it allows for better temperature control than a single condensing
unit
B. it allows for multiple evaporator temperatures to be maintained
C. it allows for greater operational safety versus a single condensing
unit
*D. all of the above
Why is it important for the oil separator to be sized properly, insulated and located as close to the compressor as possible?
to minimize the chances for refrigerant vapor to condense into liquid inside the separator
The capacity that a parallel rack will have during operation is determined by?
the coldest temperature evaporator
On a parallel compressor rack what device is used to control multiple evaporators?
EPR
What can cause the suction pressure on a parallel rack system to run higher than its setpoint?
a higher than design system load
Auxiliary contacts would not be used to?
B. control a crankcase heater
C. control an interlock circuit
What device would be used to cycle the condenser fans on and off as system head pressure changes?
a reverse acting high-pressure control
A device used to damper out compressor torque to the connected copper piping is a
vibration eliminator
A device used to maintain a minimum oil condition in a parallel rack compressor is
oil level control
To maintain the correct amount of oil in each compressor on a parallel rack an oil system would require this/these components:
A. oil separator
B. oil reservoir
C. oil level regulator
*D. all of the above
What device is used on an oil system on a parallel to control the pressure of the oil feeding the oil regulator?
pressure differential valve
What is the best method for precharging an oil separator?
charge the oil directly into the separator before brazing into place
A decrease in suction pressure of a reciprocating compressor will result in:
a decrease in volumetric efficiency
For every 1ºF of additional liquid subcooling a systems capacity will be increased by approximately?
1%