automatic reset
a switch that opens or closes in response to a change in temperature, pressure, or liquid level
manual reset
opens in response to temperature, pressure or liquid level and must be manually reset
electromechanical controls
don’t need V to operate and can switch its rated V or less
electronic controls
need electricity and specific V to operate
direct acting
a switch that OPENS on a rise or increase in temperature, pressure or liquid level
reverses acting
a switch that CLOSES on a rise or increase in temperature, pressure or liquid level
cut-out switch
a switch that opens to protect the system from short cycling
Differential
When a control switch opens b/c it’s set point is exceeded (ex: 200°F) the control will not close again until the Differential is reached (ex: 190°F) the differential is 10°F
purpose of a thermostat
to maintain a constant room air temperature
thermostat is a what kind of switch
a normally open and direct acting switch with automatic reset
nicad batteries do what in a thermostat?
charges while switch is open and uses its 24V when switch is closed
purpose of a primary control
to turn off the burner motor, ignition transformer, and oil valve if and when the flame fails
stack mounted primary responds to what?
heat of flue gases
flue gases should be between what temperatures?
300 and 900°F
cad cell primary responds to ?
yellow and orange light
cad cell in the dark needs a min of
50,000 ohms
a good flame is between ? ohms
300 and 800 ohms
trial for ignition for stack mounted primary
either 120, 90, or 60 sec (90 most common)
electronic cad cell trial for ignition
15, 30, or 45 sec (15 most common)
electromechanical cad cell trial for ignition
15, 30, 45 (45 most common)
intermittent ignition
ignition transformer is energized for full running cycle of burner
interrupted ignition
ignition transformer is de-energized w/in 1 minute of flame detection
Stack Mounted Primary (Intermittent)

Stack Mounted Primary (Interrupted)