Protectors of Conductors (From Mechanical Damage) Flashcards

1
Q

Two types of conduit (flex)

A
green field (hollow)
BX (Pre-wired)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If you cut the end of conduit what must be done?

A

an anti-short bushing (red head) must cover the cut end

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Conduit must be supported at least every __ ft

A

At least every 4 1/2 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Conduit must be supported at least __ inches within a box

A

12 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many feet of conduit can be unsupported leading to rotating machinery

A

3 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

EMT

A

Electrical metallic tubing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

All ends of EMT must be ____

A

Cut square and reamed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

EMT must be supported at least within every __ft

A

10 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

EMT must be supported within __ ft of a box

A

3 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Max bends between a box and pull fittings

A

360°

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Electrical boxes are also referred to as what?

A

Junction boxes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Junction boxes must always be what?

A

Covered and supported

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What must you do to knock out holes in the electrical box

A

Must block with knockout covers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Maximum over current protection for 14 g wire

A

15 Amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Maximum over current protection for 12 g wire

A

20 Amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

where must a switch be placed in a circuit

A

on the hot leg not on the return

17
Q

what are OHMS?

A

measurement of resistance to flow

18
Q

when a switch is closed what will the ohms meter read

A

0 Ω

19
Q

if a switch is open what will the ohms read

A

∞ Ω or OL

20
Q

to check voltage you must

A

connect to the line and neutral and if all is good next connect to the load and neutral

21
Q

you must always have a __ in a circuit

A

fuse or circuit breaker

22
Q

Oiler Burners Have a _________ switch in case of emergencies

A

emergency

23
Q

what are the rules for emergency switches

A
must be the highest switch 
must not be any higher than the first floor
in plain sight and clearly marked
markings must correlate with switch
cannot be in the same room as the boiler
24
Q

rules for thermal switches

A

must be placed directly above the burner
no higher than 6ft above the boiler
open at 165° f

25
Q

when turning on the service switch a ST must do what

A

keep hand on the service switch and stand off to the side

26
Q

Type of insulation used for (HVAC) wiring

A

THHN