PPS Setpoints Flashcards
Variable Overpower
Safety Channel NI’s 110% Power (Fixed)
- 7% above steady state (Variable)
- 6% per minute (Rate of Change) Reactor Trip
High Log Power
Middle safety Channel NI
> 10-2% (bypass permissive at 10-4%)
Reactor Trip
High Local Power Density (LPD)
Originates in CPCs
> 21 kW/ft
Reactor Trip
High Pressurizer Pressure
PT-101A-D NR
>2383 psia
Reactor Trip
AFAS Lockout
SG1 and SG2 difference > 185 psid
Low DNBR
Originates in CPCs
< 1.34
Reactor Trip
Low Pressurizer Pressure
PT-102A-D WR
< 1837 psia (variable)
Reactor Trip, SIAS, CIAS
Low Steam Generator Pressure
PT-1013A-D (SG1) PT-1023A-D (SG2)
< 960 psia (variable)
Reactor Trip
MSIS
Low Steam Generator Water Level
LT-1113A-D (SG1) LT-1123A-D (SG2) WR
< 44.2% Reactor Trip
< 25.8% AFAS
< 20.3% DAFAS
High Steam Generator Water Level
LT-1114A-D (SG1) LT-1124A-D (SG2) NR
>91%
Reactor Trip
MSIS
High Containment Pressure
PT-351A-D NR
> 3 psig
Reactor Trip
SIAS/CIAS
MSIS
High-High Containment Pressure
PT-352A-D WR
> 8.5 psig
CSAS
Low Reactor Coolant Flow
(Steam Generator D/P)
PD-115A-D (SG1) PD 124A-D (SG2)
Variable
Reactor Trip
Low RWT Level
LT-203A-D
<9.4%
RAS