PLCS and PPCS Setpoints Flashcards
Hi Level Error
+8.5% Rising - Alarm
+ 8.2% Decreasing - Alarm Reset
Low Level Error
- 3.5% Decreasing - Alarm
- 2.7% Rising - Alarm Reset
Pressurizer Level Hi-Lo Alarm
Hi Alarm @ 60%
Lo Alarm @ 25%
Normally Running Charging Pump Level Deviation
+15% Rising - Normally Running Pump Stops
+14% Decreasing - Normally Running Pump Restarts
Backup Heater Level Deviation
+3% Rising - Hi Level Deviation, B/U Heaters ON
+2.5% DEcreasing - Hi Level Deviation Reset, B/U Heaters OFF
Standby Pump Level Deviations
- 14% Rising - Standby Pump Stops
- 23% Lowering - Standby Pump Starts
PLCS Letdown Flow Limits A/M
Auto Controls 30-135 gpm (with lag in output)
Manual Controls 0-150 gpm
Pressurizer Pressure Hi-Lo Alarm
Hi Alarm @ 2285 psia
Lo Alarm @ 2160 psia
Proportional Heater Interlocks
< 25% pressurizer level - OFF
Must be manually reset (flagged) @ 27%
> 2285 psia - OFF
PZR Backup Heaters Interlocks
<25% level OFF
> 2285 psia OFF
SIAS
B/U Heater Control
<2200 psia - ON
+3% rising level deviation - ON
>2225 psia - OFF (unless in setpoint override)
+2.5% lowering level deviation - OFF
PPCS Master Controller Range
0% - Prop Htrs Full ON
- 5% - Normal Position - Prop Htrs ~50% ON
- 5% - Prop Htrs OFF, Spray Valves Closed (Start Opening)
50% - Spray Valves FULL OPEN