Power Supplies Flashcards
The Loose Parts Monitoring System (SV) system is powered from
…distribution panel NNN-D11.
The Seismic Monitoring Panel receives power from…
…distribution panel NNN-D11.
Train A Class 1E 4160 KV Bus PBA-S03 supplies power to…
SP Pump A EW Pump A EC Chiller A HPSI A LPSI A CS Pump A AF Pump N* Norm Chiller A*
Train B Class 1E 4160 KV Bus PBB-S04 supplies power to…
SP Pump B EW Pump B EC Chiller B HPSI B LPSI B CS Pump B AF Pump B
Non Class 1E 13.8 KV Bus NAN-S01 supplies power to…
RCE-P01A
RCE-P01C
CWN-P01A
CWN-P01B
Non Class 1E 13.8 KV Bus NAN-S02 supplies power to…
RCE-P01B
RCE-P01D
CWN-P01C
CWN-P01D
Non Class 1E 4160 KV Bus NBN-S01 supplies power to…
Nuclear Cooling Water Pump NCN-P01A Turbine Cooling Water PumpTCN-P01A Plant Cooling Water Pump PWN-P01A Heater Drain Pump EDN-P01B Condensate Pump CDN-P01A Condensate Pump CDN-P01B Normal Chiller WCN-E01B
Non Class 1E 4160 KV Bus NBN-S02 supplies power to…
Nuclear Cooling Water Pump NCN-P01B Turbine Cooling Water Pump TCN-P01B Plant Cooling Water Pump PWN-P01B Heater Drain Pump EDN-P01A Condensate Pump CDN-P01C Normal Chiller WCN-E01C Small Normal Chiller WCN-E02
Normal Control Power for 13.8 KV, 4160 KV, and 480 VAC Loadcenters is supplied by
NKN-D41
NKN-D42
480 VAC MCC’s are supplied control power from…
a transformer downstream of the circuit breaker.
Non Class 1E 125 VDC NKN-M45 supplies power to…
Plant Computer Inverter Distribution Panel NKN-D41 Distribution Panel NKN-D42 Distribution Panel NKN-D43 NAN-S05 Control Power (normal) NAN-S06 Control Power (alternate) Main Generator Primary protection circuits Main Generator Backup protection circuits
Non Class 1E 125 VDC NKN-M45 supplies power to…
Main Turbine EBOP Main Generator ESOP Main Feedwater Pump “A” Emerg LO pump Main Feedwater Pump “B” Emerg LO pump NAN-S06 Control Power (normal) NAN-S05 Control Power (alternate) Normal Access Personnel Air Lock Emerg Access Personnel Air Lock Distribution Panel NKN-D44 Distribution Panel NKN-D45
RCP breaker control power is supplied from…
Non-Class 125 VDC NKN-D44
Stator Cooling Water Pump P01A and P01B are supplied power by…
Non-Class IE 480 VAC NGN-L15 and L14
Control power for the intermediate buses NAN-S05 and NAN-S06 is supplied by
NAN-S05 from NKN-M45 normal, NKN-M46 alternate
NAN-S06 from NKN-M46 normal, NKN-M45 alternate