State the possible characters for the second position in the electrical distribution system nomenclature.
example: PBA-SO3

A
A - 13.8 KV
B - 4.16 KV
G - 480 VAC LC
H - 480 VAC MCC
K - 125 VDC
N - 120 VAC INST
E - 4.16 KV DG
Q - 120 VAC UPS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

State the possible characters for the first position in the electrical distribution system nomenclature.
example: PBA-SO3

A

N - Non-Class

P - Class

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State the possible characters for the third position in the electrical distribution system nomenclature.
example: PBA-SO3

A
A - Train A
B - Train B
C - Train C
D - Train D
N - Non Train
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State the possible characters for the fourth position in the electrical distribution system nomenclature.
example: PBA-SO3

A

D - Distribution Panel
M - Motor Control Center (Bus - generally < 50 HP loads)
L - Load Center (generally > 50 HP loads)
S - Switchgear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State the possible characters for the last two positions in the electrical distribution system nomenclature.
example: PBA-SO3

A

The last two numbers are particular to the equipment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is required for NAN-S01 and NAN-S02 Fast Bus Transfer to NAN-S03 and NAN-S04?

A
  1. The ‘BUS XFR SWITCH’ must be in AUTO
  2. Generator trip must have occurred
  3. Early ‘b’ contact on NAN-S01 normal supply breaker must
    be closed
  4. Synch Check relay must be satisfied
  5. No bus lockout (86)