State the possible characters for the second position in the electrical distribution system nomenclature.
example: PBA-SO3
A - 13.8 KV B - 4.16 KV G - 480 VAC LC H - 480 VAC MCC K - 125 VDC N - 120 VAC INST E - 4.16 KV DG Q - 120 VAC UPS
State the possible characters for the first position in the electrical distribution system nomenclature.
example: PBA-SO3
N - Non-Class
P - Class
State the possible characters for the third position in the electrical distribution system nomenclature.
example: PBA-SO3
A - Train A B - Train B C - Train C D - Train D N - Non Train
State the possible characters for the fourth position in the electrical distribution system nomenclature.
example: PBA-SO3
D - Distribution Panel
M - Motor Control Center (Bus - generally < 50 HP loads)
L - Load Center (generally > 50 HP loads)
S - Switchgear
State the possible characters for the last two positions in the electrical distribution system nomenclature.
example: PBA-SO3
The last two numbers are particular to the equipment.
What is required for NAN-S01 and NAN-S02 Fast Bus Transfer to NAN-S03 and NAN-S04?
- The ‘BUS XFR SWITCH’ must be in AUTO
- Generator trip must have occurred
- Early ‘b’ contact on NAN-S01 normal supply breaker must
be closed - Synch Check relay must be satisfied
- No bus lockout (86)