What is the P-4 Permissive?
P-4 (Reactor Trip)
Rx Trip AND Bypass Breakers Open
Functions:
- Trips Main Turbine
- Feedline Isolation (w/ Tavg LO [564 °F])
- Prevents SI re-actuation after SI reset
- Transfers steam dumps from load rejection to plant trip
- Permissives / Control Interlocks*
- *
What is the P-6 Permissive?
P-6 (Source Range)
IR > 1x10-10 amps [1/2]
Function: Allows MANUAL block of SR Neutron Flux-HI Rx Trip (1x105 CPS [1/2])
- Note: AUTO Block of SR Neutron Flux-HI occurs at P-10 (PR > 10%) [2/4].*
- Permissives / Control Interlocks*
- *
What is the P-7 Permissive?
P-7 (At Power Permissive)
P-10 or P-13 [1/2]
Functions: AUTO unblocks the following Rx Trips:
- Pressurizer Pressure- LO (1885 PSIG [2/4])
- Pressurizer Level-HI (92%) [2/3]
- RCP UV (10584 VAC) [1/2 RCPs on 2/2 Buses]
- RCP UF (57.2 HZ) [1/2 RCPs on 2/2 Buses]
- RCS Flow-LO (90%)
[2/3 on (2/4 < P-8) OR (1/4 > P-8)]
- Permissives / Control Interlocks*
- *
What is the P-8 Permissive?
- *P-8 (Loop Flow Permissive)**
- *PR > 48% [2/4]**
Functions: AUTO changes coincidence of RCS Flow-LO (90%)
- > P-8 [2/3 on 1/4]
- < P-8 [2/3 on 2/4]
- Permissives / Control Interlocks*
- *
What is the P-9 Permissive?
P-9 ( Turbine Trip / Rx Trip)
PR > 50% [2/4]
Function: AUTO unblocks Rx Trip on Turbine Trip
- Permissives / Control Interlocks*
- *
What is the P-10 Permissive?
- *P-10 (Nuclear at Power Permissive)**
- *PR > 10% [2/4]**
Functions:
- Input to P-7
- AUTO blocks SR Neutron Flux-HI (1x105 CPS) [1/2]
- Allows MANUAL block:
- IR Neutron Flux-HI (25%) [1/2]
- PR Neutron Flux-LO (25%) [2/4]
- C-1 (20%) [1/2]
- Note: MANUAL Block of SR Neutron Flux-HI performed at P-6 (IR > 1x10-10 AMPS) [1/2].*
- Permissives / Control Interlocks*
- *
What is the P-11 Permissive?
P-11 (Pressure SI Permissive)
< 1970 PSIG [2/3]
Functions:
Allows MANUAL Block:
- PZR Pressure-LO (1885 PSIG) [2/4]
- (Rx Trip)*
- MSL Pressure-LO (615 PSIG) [2/3 on 1/4]
- (SI / SLIS)*
- Note: > P-11 AUTO unblocks PZR Pressure-LO and MSL Pressure-LO*
- Permissives / Control Interlocks*
- *
What is the P-12 Permissive?
- *P-12 (Tavg LO-LO Permissive)**
- *550ºF [2/4]**
Function: Blocks Steam Dumps
- Permissives / Control Interlocks*
- *
What is the P-13 Permissive?
P-13 (Turbine at Power Permissive)
P<span>imp</span> > 10% [1/2]
Function: Input to P-7
- Note: OTO-SA-00001 lists P<span>imp</span> > 60 psig [1/2]*
- Permissives / Control Interlocks*
- *
What is the P-14 Permissive?
P-14 (S/G Level HI Permissive)
SG NR Level > 91% [2/4 on 1/4]
Functions:
- FWIS
- Trips Main Turbine
- Trips MFPs
- Permissives / Control Interlocks*
- *
What is the C-1 Control Interlock?
C-1 (IR Rod Stop)
20% IR amps [1/2]
Function: Prevents MANUAL rod withdrawal.
- Note: MANUAL rod insertion and AUTO rod withdrawal / insertion are not effected.*
- Permissives / Control Interlocks*
- *
What is the C-2 Control Interlock?
C-2 (PR Rod Stop)
103% [1/4]
Function: Prevents MANUAL rod withdrawal.
- Note: MANUAL rod insertion and AUTO rod withdrawal / insertion are not effected.*
- Permissives / Control Interlocks*
- *
What is the C-3 Control Interlock?
C-3 (OTΔT Rod Stop)
OTΔT Setpoint -2% [2/4]
Function:
- Prevents MANUAL rod withdrawal.
- Causes main turbine runback
- Note: MANUAL rod insertion and AUTO rod withdrawal / insertion are not effected.*
- Permissives / Control Interlocks*
- *
What is the C-4 Control Interlock?
C-4 (OPΔT Rod Stop)
OPΔT Setpoint -2% [2/4]
Function:
- Prevents MANUAL rod withdrawal.
- Causes main turbine runback
- Note: MANUAL rod insertion and AUTO rod withdrawal / insertion are not effected.*
- Permissives / Control Interlocks*
- *
What is the C-5 Control Interlock?
C-5 (Low Power Interlock)
P<span>imp</span> < 15% [1/1]
Function: Original plant design stopped AUTO rod withdrawal.
- Note:*
- PT-0505 only
- Removed by CMP 95-1008.