For all single-phase motors, to protect them from short circuits and ground faults, a multiplying factor of _____ of its full load current rating shall be used the protective device selected is a non-time delay fuse and _____ if the protective device is a time delay fuse.
300%, 175%
Flexible metal conduit shall be supported within ____ on each side of every outlet box, junction box, cabinet or fitting.
300 mm
The maximum electrical trade size of electrical metallic tubing shall be_____.
100 mm
For installations of 2.0 mm2 conductors in 600-v circuits, what is the minimum insulation resistance allowed by the Philippine Electrical Code?
500,000 Ω
Askarel insulated transformers installed indoors and rated over ____ kVA shall be furnished with a pressure relief vent.
25
In straight pulls, the length of the pull box shall not be less than _____ times the trade diameter of the largest raceway.
8
Busways shall be securely supported at intervals NOT exceeding ____ unless otherwise designed and marked.
1,500 mm
The smallest electrical trade size of a liquidtight flexible non-metallic conduit shall be.
20 mm
Boxes intended to enclose flush devices shall have an internal depth of NOT less than ____.
24 mm
A branch circuit supplying a fixed storage type water heater having a capacity of 450 liters or less shall have a rating not less than _____ of the nameplate rating of the water heater.
125%
Defined as the shortest distance measured between a point on the top surface of any direct buried conductor, cable, conduit and the top surface of finish grade.
Cover
A wall screen or fence less than ____ in height shall NOT be considered as a preventing access unless it has other features that provide a degree of isolation equivalent to the height of the fence in question.
2,500 mm
Branch circuit conductors supplying a single phase motor shall have an ampacity NOT exceeding
125%
Pits within ____ horizontally from the flammable vapor source, shall be considered a hazardous location under Class I, Division I location
7,600 mm
Type TW conductor is a ____ type.
A. moisture and heat resistant
B. moisture and heat resistant thermoplastic
C. moisture resistant and thermoplastic
D. heat resistant and thermoplastic
C. moisture resistant and thermoplastic
The current in amperes a conductor can carry continuously under the conditions of use without exceeding its temperature rating
Ampacity
Flat conductor cables maybe installed in any of the following location EXCEPT one. Which one is this?
In wet locations
Operation of loads and intervals of time both of which maybe subject to wide
Varying duty
For equipment rated 1200 A and over 1,900 mm wide containing overcurrent devices and control devices at least one entrance of NOT less than ____ wide and ____ high shall be provided at each end.
600 mm, 2,000 mm
Batteries and direct current circuits shall be physically separated by at least a ___ gap or other approved means from circuits of a different power source.
12 mm