PEC 11 Flashcards
A convenience outlet circuit consisting of 8 outlets connected across a 220-V supply considering 180W per outlet, what is the maximum circuit current?
6.54 A
Plug fuses and fuse holders shall NOT be installed or such in circuit’s exceeding ____ between conductors.
250 V
The standard length of rigid metal conduit is
10 feet
For warehouse, the feeder demand load for the general lighting and small appliance load for the first 12,500VA or less is 100%, while the remainder over 12,500VA is charged at ____.
70%
Liquid tight flexible non-metallic conduit shall NOT be used in lengths longer than
1,800 mm
Line and ground connecting conductors to surge arresters shall NOT be smaller than ______ copper or ______ aluminum.
2.0 mm², 3.5 mm²
Electrical metallic tubing shall be securely fastened in place at least every______.
3,000 mm
For the purpose of lighting protection, class I ordinary building is one that is at less than_____ in height.
23 m
For dwelling units, the demand factor for the first 3000 voltamperes of load is
100%
Ventilating pipes for motors, generators or other rotating electric machinery or for enclosures for electric equipment shall be of metal NOT less than _____ in thickness.
0.50 mm
Direct burial cables or conductors with nominal voltage of 600V or less and passes under streets, hi-way, roads, alleys, driveways and parking lots shall have a minimum cover distance of ____
600 mm
A factor assembly of parallel conductors formed integrally with an insulating _____ material web specifically designed for field installation in metal surface raceway.
type FC
Snap switches shall not be grouped or ganged in enclosures unless they can be so arranged that the voltage between adjacent switches does not exceed ____.
300 V
Wiring located above heated ceilings shall be spaced not less than ____ above the heated ceiling and shall be considered as operating at an ambient of 50°C.
50 mm
Are rectangular sheet metal enclosures equipped with removable covers providing access to conductors inside
Wireways
Each unit length of heating cable shall have a permanent legible marking of each non-heating lead located within ____ of the terminal end.
75 mm
Metal faceplates of receptacles shall be of ferrous metal not less than ____ in thickness or of non-ferrous metal not less than ____ in thickness.
0.76 mm, 1.0 mm
Surface mounted incandescent fixture shall be permitted to be installed in clothes closets provided there is a minimum clearance of _____ between the fixture and the nearest point of the storage area.
300 mm
Thermal insulation shall not be installed within _____ of the recessed fixture enclosure.
38 mm
Lighting track load shall NOT be installed where less than _____ above the finished floor EXCEPT where protected from physical damage.
1,500 mm