PCCW Flashcards

1
Q

State PCCW normal temps and basis

A

Train A: 65-75 for VCT and Seal injection temperature

Train B: 65-78 to help reduce containment temperature since we run fairly close to upper limit of 120F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State PCCW high temp trip

A

135F for 60 seconds (2/2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State PCCW auto start feature

A

30 second time delay and

NO high temperature in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is a Thermal Barrier HX Leak isolated

A

Flow element alarms at 71 GPM
NSO energizes MOV and valve auto closes
Other loops of TB may alarm due to increased flow after 1 loop is isolated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State how EPS interacts with CC pumps

A

The Running PCCW pump will start at SR4
If 2 pumps in same loop were running preferred pump will start
To start standby pump EPS must be reset or RMO reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Discuss how the PCCW TCV and Bypass work together to cool PCCW

A

The two valves modulate together to maintain temperature per setpoint on the MCB.
On full flow HX outlet opens and HX bypass closes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Discuss how PCCW responds on a T-Signal

A

Isolates: LTDN HX, SF HX, WPB.

Initiates CC to RHR HX

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Discuss how PCCW responds on a P-Signal

A
Isolates containment (not TB)
Initiates CC to CBS HX
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State how PCCW responds on a Low head tank level Setpoint and coincident

A

<42% 2 of 3 on 1 of 2 trains

Isolates WPB and Rad monitors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

State how PCCW responds on a Low-Low Head tank level, Setpoint and Coincident

A

<36% 2 of 3 on 1 of 2 trains

Isolates containment, not TB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Discuss why MCB PCCW Flow indication does not represent total system flow

A

The flow element is down stream of:
SFHX
EAH AC units
CCP oil coolers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly