P&Ls Flashcards
1
Q
What is the precaution associated with heater cooldown prior to shutdown of an AEGTS fan?
A
Verify the heater has been deenergized for a minimum of 5 minutes to allow cooldown.
2
Q
What is the precaution associated with charcoal temperature?
A
Ensure charcoal temperature remains below 300F. This temperature is a potential indication of a charcoal fire.
3
Q
Where is it desirable to maintain Annulus pressure?
A
Normal band is 0.75”-1.0” H2O, and it’s desirable to maintain as close to 0.75” as possible to minimize leakage out of the Containment during post accident scenarios.