What is the purpose of the Annulus Exhaust Gas Treatment System?
Maintain Annulus pressure at a slight negative pressure to ensure any Containment Vessel or Shield Building leakage is into the Annulus.
Filter any airborne radioactive Iodine and particulates form the air which leaks out of the Containment Vessel.
Monitor exhaust gases prior to release to the atmosphere.
What is the normal differential pressure maintained in the Annulus?
0.75 - 1.0 Inches of Water vacuum.
What components makeup the Annulus Exhaust Gas Treatment system Exhaust Plenum?
Demister –> Roughing Filter –> Electric Heating Coil –> HEPA Filter –> Charcoal –> HEPA Filter.
What is the purpose of the Demister in the AEGTS Exhaust Plenum?
Remove water droplets and large particles entering the plenum.
What is the purpose of the Roughing Filter in the AEGTS Exhaust Plenum?
Removes large particles from the process stream.
What is the purpose of the Electric Heating Coil in the AEGTS Exhaust Plenum?
Reduces humidity thereby increasing the efficiency of charcoal adsorption.
What is the purpose of the HEPA Filter in the AEGTS Exhaust Plenum?
Removes fine particles from the process stream to increase the efficiency of charcoal adsorption.
What is the purpose of the Charcoal in the AEGTS Exhaust Plenum?
Removes radio-iodine in the process stream.
What is the purpose of the second HEPA Filter in the AEGTS Exhaust Plenum?
Removes charcoal fines.
What is the rated flow for each Annulus Exhaust Gas Treatment Fan?
2000 scfm
What is the power supply for the Annulus Exhaust Gas Treatment Fans?
A: EF-1-B
B: EF-1-D
What are the start permissives for the Annulus Exhaust Gas Treatment Fans?
There is ONLY one: Deluge Switch NOT ARMED.
What will cause the Annulus Exhaust Gas Treatment Fans to automatically start?
1) RHR LOCA(16.5 inches RPV level and/or 1.68 psig Drywell pressure)
2) Low flow on the running fan.
What is the value for the Low Flow automatic start of the Annulus Exhaust Gas Treatment Fans?
Less than 1500 scfm, the alarm comes in when flow is less than 1650 scfm.
Can the Low Flow automatic start be overridden?
NO, the standby fan that auto started can be stopped with the control switch, but as soon as its released the fan will restart if the low flow condition still exists.