Open/Closed Blowdown Flashcards
1
Q
Discuss Blowdown.
A
- 40 gpm / SG
- Closed blowdown flow is cooled by the Open Blowdown system.
- Open Blowdown system cooled by ICW (prevents release)
2
Q
Discuss Open and Closed Blowdown Cooling Systems.
A
- Non Safety Related
- Loss of demin water results in loss of makeup water source to the closed blowdown system (Makeup water to surge tank / Chemical Feed Pot through auto LCV or manual valve)
- Blowdown AOV’s fail closed on loss of air (with exception of ICW to OBCS HX, fail OPEN)
3
Q
Discuss Closed Blowdown Cooling Pumps.
A
‘A’ Pump: MCC {1A2} [2A1]
‘B’ Pump: MCC {1B2} [2B1]
Local control only, Start-Stop pushbutton at PP & Control Switches in SGBTF
4
Q
Discuss Closed Blowdown Cooling Surge & Chemical Feed Tank.
A
- Located on the 62’ elevation of the Turbine deck. Provides NPSH for pumps
- Tank M/U from Demin Water. Auto LCV-34-1 controls level -2” to +4” of tank centerline
- Feed Pot located next to surge tank. Allows chemical addition for corrosion control
- Local level indication only
5
Q
Discuss Closed BD HX.
A
- Purpose: Reduces S/G blowdown water from a temperature of approximately 550ºF to 120ºF
- Three sets of two ® “A – B – C”. Normally two HX sets in operation with the third in standby
- The CBCS Hx are located on the RAB roof on the 43’ elevation (SNPO land).
- CBCS water makes a single pass through the shell side of each HX
- OBD cooling water flows through the tubes
Designed to handle heat loads from S/G B/D between 25 – 125 gpm per SG (normal 40 GPM)
Open blowdown flow enters at 100ºF, exits at 172ºF before returning to shell side of the OBCS Heat Exchangers - If blowdown exceeds 140ºF downstream of the HX, blowdown isolates (TCV-23-8 will close to protect the SGBTF Demineralizer)
- NOTE: TCV-23-8 is common BD ISOL valve to SGBTF (1 valve / unit)
- PCV Maintains 300#
- Enters at 100ºF, exits at 172ºF before returning to shell side of the OBCS Heat Exchangers
- 700 gpm per heat exchanger
6
Q
Discuss Open BD HX.
A
- Provides the heat sink for the heat removed from the S/G blowdown.
- (2) single pass heat exchangers located on north side of the Turbine Building mezzanine level
- Lined up in parallel, both in service
- CBCS water flows through the shell side of the HX, cooled from 172°F to 100°F
- ICW flows through the tube side of the heat exchanger
- TCV-34-3A & 3B – located in the ICW piping on the outlet side of the OBCS HX’s
- Automatically vary the flow of ICW through the tube side of the OBCS HX’s in response to control air signals sent from TIC-34-3A & 3B
- Regulating setpoint of 90°F
- OBDHX TCV’s fail open (full cooling) on:
a) Loss of instrument air
b) Loss of electrical power. - ICW supply valves to OBDHX’s (MV-21-2 and 21-3) fail “as is” on a loss of power
7
Q
Discuss normal blowdown operation.
A
- 2/3 CBHX’s are in service anytime a CBCS Pump is in operation
- When Isolating one CBHX, always place the spare heat exchanger in service first and allow for heat up time if possible
- Maximum combined (U1 + U2) blowdown flow is limited to 300 GPM to prevent channeling of resin beds in the SGBTF
- If Closed Blowdown Cooling flow lost to the CBHX, blowdown must be immediately isolated
- Loss of Instrument Air – All AOV’s fail closed with exception of the OBHX TCV’s fail open
- Unit 2 SNPO covers the Blowdown Building
- Monitor Storage Tank used for SGBD minimum level is 10 FT to preclude sucking air into the condenser, which could occur @ ~ 5 ft