Nfpa72 Flashcards

1
Q

Shall a system with a positive alarm sequence be provided the means to bypass the positive alarm sequence?

A

Yes, it shall. 23.8 system requirements

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A Dact shall be programmed to call a second DACR telephone number if unable to connect to the 1st number?

A

Yes it shall, 26.6 Communication methods/Transmission signals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which signal type has the highest priority?

A

Fire alarm signal 10.7.2 fundamentals/signal priority

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

There is no limit to the number of DACT that can Communicate to a single DACR?

A

False, depends on the # of telephone lines 26.6 communication methods/transmission signals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the maximum time in seconds between initiating of an alarm at the protected premises and display at the supervising station?

A

90 seconds 14 inspection/testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A single spare DACR can be used as backup to how many active DACRS?

A

Up to 5 DACRS 26.6.4.2.1 Equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Trouble signals shall restore within how many seconds?

A

To 200 seconds 10.14 fundamentals/trouble signals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An alarm signal shall be indicated within how many seconds of a water flow?

A

90 seconds 17.12 initiating devices sprinkler water flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Duct detectors are required on the supply side for Hvac it’s rated at what CFM?

A

Over 2000 CFM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

FPLP able can be used in riser applications?

A

Yes NEC ch.7 part IV chart

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If you are using a 16’ extension ladder, how many feet must the 2 halves overlap when fully extended?

A

3ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Required signals shall not be lost interrupted or delayed more than how many seconds as a result of primary power failure?

A

10 seconds 10.6.6.3 fundamentals/power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The secondary power supply shall have a sufficient compacity to operate the fire alarm system under quiescent load for a minimum of how many hours? And at the end of that period shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location and emergency for how many minutes?

A

Power supply should be sufficient for 24 hours. And after that notification appliances work for 5 minutes. 10.6.7 power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What’s may provide power for the primary power of a fire alarm system ?

A

Branch circuit, electric utility, engine driven generator with trained operator on duty. 10.6.5.1 fundamentals/power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The NFPA 72 States the maximum spacing for smoke detectors and absence of other engineering data is how many feet?

A

30ft 17.7.3.2.3.1 initiating devices /smoke sensory fire detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A central station is defined as what

A

Central supervising station

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Shall a DACT seize the telephone line when it’s required to transmit a signal?

A

Yes 26.6 supervising station alarm systems/requirements for DACTs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What is the minimum number of telephone lines that’s DACR shall have?

A

2 separate incoming telephone lines 26.6.4.2.2 Supervising station alarm systems/communication methods

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the time interval that a DACT shall transmit a signal to the DACR?

A

4 hour intervals. When alarm is initiate it 90 seconds. 26.6.4.1 point for supervising station alarm systems/communication methods

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

When testing the primary battery load for a number 6 battery it shall not exceed how many amperes per cell?

A

Depends on manufacture recommendations? 14.4.3.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What methods/tests shall be performed on smoke detectors to insure that they are within the listed and marked sensitivity range?

A
  1. calibrated 2. manufactures calibrated test in an instrument 3. control unit arrangement 4. other calibrated test approved by authority
  2. 4.3.2 chart sensitivity Testing
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Records of testing shall be retained until the next test date and how long after?

A

Next test and one year thereafter 14.6.2.1 maintenance inspection and testing records

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Can electronic media be used for retaining inspection records?

A

Yes 14.6.2.1 Inspection/testing records

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What class pathways are required to have a primary and redundant pathway?

A

Class A and X.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Upon failure of the primary power supply within how many seconds must the secondary power supply provide power to the system of a supervising station?

A

60 seconds 10.6.6.2 power fundamentals/power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

The standard fire alarm evacuation signal is how many pulses and what pattern type?

A

A 3 pulse temporal pattern 18.4 audible characteristics

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Initiating device circuits that transmit an alarm Or supervisory signal and allow all connected devices to operate during a single open is considered as what type of circuit?

A

Class A and X

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Shall a system with a positive alarm sequence be provided the means to bypass the positive alarm sequence ?

A

Yes system shall have means for bypassing 23.8.1.2 system requirements

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

The secondary power supply shall provide power to the protected premises within how many seconds upon failure of the primary power source?

A

Within 10 seconds 10.6.6.1 fundamentals/power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

Required signals shall not be lost or delayed for more than hope many seconds as a result of primary power failure?

A

10 seconds 10.6.6.3 continuity of power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

What is the maximum allowable voltage for NPLFA circuit?

A

? Nec 760.41

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

How far from the end of a 20ft wide corridor shall a visible notification device be?

A

No more then 15ft 18.5.5.5.5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

What would be the minimum depth of a non-metalicraceway without concrete encasement be installed under a parking garage?

A

24 inches NEC back book Raceway-underground-ect.

34
Q

Where would the Sequence of operation be found?

A

At the control panel

35
Q

Heat detectors shall be selected to for maximum expected ambient ceiling temperature and shall be at least how many degrees above Max ambient?

A

20°F. 17.6.2.3 Initiating devices - heat sensing for detectors

36
Q

What would the temperature range be of a fixed type spot heat detector with a white color code bend be?

A

Intermediates 175 - 249°F/ 80-121°c

17.6.2.1 initiating devices/ heat sensing for detectors

37
Q

When shall smoke detector sensitivity be re calibrated after a new installation?

A

After one year of install 14.4.4.3 testing

38
Q

If voltage is doubled and resistance is halved what is the effect on the current?

A

Current increases

39
Q

The term shall when used in the national fire alarm code indicates what?

A

A mandatory requirement. definitions

40
Q

What is the maximum size ground conductor for telecommunications circuit?

A

Shall not exceed 6 AWG NEC back book/communications grounding

41
Q

What color should an insulated ground conductor size no.6 equipment grown be ?

A

Green? NEC 250.119 back book, conductors/grounding/identification

42
Q

A manual pull station shall be mounted within how many feet of an exit doorway?

A

5ft. 17.14.8.4 Initiating devices

43
Q

What is the range in inches that a manual pull station shall be mounted at?

A

42 - 48 inches off floor 17.14.5 initiating devices

44
Q

Where fire detectors are installed in a concealed locations more than 10ft above the finished or in arrangements where the detectors alarm or supervisory indicator is not visible to responding personnel, the detectors shall be provided with what additional means?

A

With a remote alarm or supervisory indication. 17 initiating devices/general requirements

45
Q

Smoke alarms shall not remain in service after how many years from the dates of manufacture, unless otherwise provided by the manufacturers published instructions?

A

10 years 14.4.5.4.1 testing/smoke/single multiple station devices

46
Q

A lobby smoke detector shall be located on the ceiling within how many feet of the center line of each elevator lobby door within the elevator bank under control of the detector?

A

21feet

21.3.5 emergency control functions/elevator phase 1 recall

47
Q

Can a water flow switch be permitted to initiate elevator phase one emergency recall operation?

A

Yes 21.3 elevator phase one emergency recall operation

48
Q

Failure of any equipment that is critical to the operation of the fire alarm system or emergency control function interface devices shall be indicated at the master fire alarm control unit within how many seconds?

A

To 200 seconds 10.14 fundamentals/trouble signals

49
Q

Can fire alarm systems be permitted to share components, equipment, circuitry, and installation wiring with non fire alarm systems?

A

Yes

50
Q

The number of supervisory signal initiating devices permitted to be connected to a single initiating device circuit shall not exceed how many devices?

A

20 devices 23.5.6.2 protected promise fire alarm systems/system requirement

51
Q

Are fire detectors required in spaces that are protected by an automatic fire suppression system?

A

Yes 23.11.7 protected promise fire alarm system /suppression system actuation

52
Q

Each low power radio Transmit/trasceiver Shall automatically repeat alarm transmissions at intervals not exceeding how many seconds?

A

60 seconds 23.16 .3.2 protected promise fire alarm/requirements for low power radio

53
Q

Riser Coaxial cables shall be rated as riser cables and routed through a rated enclosure for what amounts of hours?

A

2 hours

54
Q

Unless configured in compliance with 10.6.4 how many independent and reliable power supplies shall be provided in a fire alarm system?

A

2 independent shall be supplied. One primary and 1 secondary 10.6.3.2 fundamentals/power supplies

55
Q

Where shall the location of the branch circuit disconnecting means be permanently identified at?

A

At the control unit 10.6.5.2 circuits/disconnecting means

56
Q

Is monitoring required for the neutral of a 3, 4, or 5 wire AC or DC supply source serving remotely located control equipment?

A

No 10.6.9.1.4 fundamentals/power supplies/monitoring integrity

57
Q

Supervising station alarm systems shall be arranged to delay the transmission of primary power failure signals for how long?

A

60 - 180 minutes unless a delay is not permitted by AHJ 10.6.9.3

58
Q

Batteries shall be installed with the month/year of installation date?

A

False they shall be installed manufacture date. 10.6.10 power supplies/storage batteries/marking

59
Q

What are the 2 types of charging methods of batteries serving fire alarm power supplies?

A

Trickle charge and float charge 10.6.10.3.4 Power supplies/battery charging

60
Q

The service provider shall report to the authority having jurisdiction of any system that is out of service for more than how many hours?

A

For more than 8 hours 10.20.4 Fundamentals/impairments

61
Q

At what periodic frequency must fiber optic cable connections be inspected/tested?

A

Inspected Semi annual. NA for testing 14.3.1 inspection/testing

62
Q

At what periodic frequency must nickel - Cadmium batteries be inspected/tested?

A

Inspected semi annual Tested Annually 14.4.3.2 chart inspecting testing batteries

63
Q

Duct detectors must be installed in accordance with what to code books?

A

NFPA 72 and NFPA 90A

64
Q

The number of sprinkler flow valves on a single zone shall not exceed more than what’s amount?

A

20

65
Q

Spacing of a smoke detector in a hallway 10feet wide or less shall be how many feet?

A

41feet? Or = or less than 0.7 times the nominal 30ft spacing

66
Q

When inspecting duct detectors list the method of inspection to be conducted

A

Table 14.3.1 inspection testing/inspection duct table method test through sampling tube

67
Q

The off normal signal shall be initiated for a pressure tank when the required pressure increases or decreases by how many PSI?

A

10PSI 17.16.2.2.1 initiating devices - supervisory signal - pressure tank

68
Q

The off normal signal shall be initiated for a water tank when the water levels fall or rises how many inches?

A

Falls 3” or rises 3” 17.16 .3.2.1 initiating devices-levels supervisory signal

69
Q

The maximum light pulse duration shall be how long and with a maximum duty cycle of what percent?

A

Max duration 20 milliseconds Max duty cycle 40% 18.5.3.2 notification appliances - visible characteristics - light color and pulse

70
Q

Lights used for fire alarm signaling only or to signal intent for complete evacuation shall be clear or nominal white and shall not exceed how many candela?

A

1000 cd=candela. 18.5.3.4 notification appliance - visible characteristics - light color pulse

71
Q

Where low ceiling heights do not permit wall mounting at a minimum of 80 inches, wall mounted visible appliances shall be mounted within how many inches of the ceiling?

A

6” inches 18.5.5.2

72
Q

In a corridor application, visible appliances shall be rated not less than how many candela?

A

15 cd 18.5.5.5.3 spacing

73
Q

In a sleeping area for rooms with a linear dimension greater than 16feet the visible notification appliance shall be located within how many feet from the pillow?

A

16feet 18.5.5.7.3

74
Q

Emergency control function interface devices shall be within how many feet of the components controlling the emergency control function?

A

3 feet (1m) 21.2.4

75
Q

What is the minimum length of a grounding rod?

A

8feet. NEC 250.53 Back of book

76
Q

When working under overhead power lines what is the minimum distance of clearance one must maintain?

A

10feet

77
Q

Where multiple control units of the same manufacturer are interconnected in a network arrangement and serve the same protected Premises, the control units shall be a ranged to be reset or silenced from how many locations?

A

1 location 23.8.2.9 protected premises fire alarm system - system requirements. Found in back of book

78
Q

The system installer shall provide evidence of their qualifications when requested by whom?

A

When requested by the authority having jurisdiction. Fundamentals - personal qualifications 10.5.2.5

79
Q

If ceiling heights allow, and unless otherwise permitted by 18.4.8.2 through 18.4.8.5, wall mounted appliances shall have their tops above the finished floors at heights of not less than how many inches?

A

90 inches 18.4.8.1

80
Q

Is signal receiving equipment required to indicate receipt of each signal both audibly and visually?

A

Yes. 27.5.2.2.5