Blue Card X2 Flashcards
A fire alarm system using automatic fire detection or water flow detection devices must be equipped with what?
A manual pull station
23.8.5.1.2
Back of book under Automatic fire detectors
A single open or single ground fault condition on a SLC shall be annunciate in within how many seconds?
200 seconds
10.14 fundamental trouble signals
All devices and appliances that received their power from IDC or us else I shall be listed to work properly with
The control unit. Chapter 10?
An FACP must be able to operate its normal functions between how many ゚F
32 - 120゚F
10.3.5 fundamentals. equipment.
Equipment must be engineered and tested to operate properly at how many percent of its name plate voltage
85%
10.3.5 fundamentals. equipment.
All devices and appliances that receive their power from the IDC or SLC shall be listed to work properly with what?
The control unit
If a reliable source of fuel for an engine ? and generator is available at any time with a 2 hour notice, it shall be permitted to have fuel in storage sufficient for how many hours of operation at full load?
12 hours
10.6.11.6.3 fundamentals. Power supplies.engine driven generators
Recharging batteries must be completed within how many hours after a single discharge has been completed?
48 hours.
10.6 power supplies. Battery charging
A protected promise is system operating under secondary power must be capable of How many hours under normal operation and minutes in alarm?
24 hours. 5 min
The secondary power supply must be able to operate the fire alarm system under normal load for a minimum of how many hours and then it must have sufficient power to operate all alarm NAC devices use for evacuation or relocation in the event of an emergency for how many minutes?
24hour 5 min
Which of the following is an acceptable source for primary power of a fire alarm system?
An engine driven generator where a person specifically trained in its operation is on duty at all times.
Not a dedicated commercial light or power branch circuit
Which of the following is not required to identify the circuit disconnect means for a fire alarm system?
10.6.5.2 power supplies. Circuit identification and accessability
The class of circuit on a fire alarm system that has a redundant path, allowing devices downstream from a short to function properly is what class of circuit?
Class A
All 3 types of signals on a fire alarm system are all of the following except A. Supervisory B.Trouble C.EVAC D. Alarm
C.Evac
The 2 circuits found on an addressable fire alarm system are the notification appliance circuit and the ____?
SLC
Signaling line circuits
The 2 circuits found on a conventional fire alarm system are the notification device circuit and the ___?
IDC
Initiating Device Circuit
The type of fire alarm system that utilizes zones with multiple and initiating devices instead of specific numbers for each individual device is called A ____ sytem.
Conventional
A class A requires the use of end of line resistor (EOLR) True or False?
False. It is redundant and can loop back to panel.
The main purpose of fire protection is to identify a developing fire in a timely manner, alert the building occupants, and notify local fire emergency organizations (if applicable).
True or false?
True
What class circuit pathway has a fail safe operation that maintains integrity were no fault is annunciated?
Class D
12.3 circuits and pathways
Are all circuit classes required to be monitored for integrity?
No.
12.6 circuit pathways. Monitoring
Installation conductors shall be monitored for integrity. The occurrence of a single open or single ground fault condition shall be automatically indicated within how many seconds?
200 seconds.
12.6 circuit pathways. Monitoring
If a fire alarm system has a malfunctioning circuit that is not corrected at the completion of an inspection, test, or maintenance. the _____ must be notified within 24 hours in writing.
Building owner
Testing of all circuits extending from central station must be completed at intervals of no more than how many hours?
24 hours 14.4.7
Back book. Central station or circuits. Testing
Water storage containers used to supply fire sprinklers must not freeze common if the water temperature drops to this level a supervisory signal must be actuated at the panel?
40°F. 17.16.4.2
Back of book. Water temperature supervision
What is the proper method to perform a ground fault test?
Grounding a conductor on the initiating circuit. And also grounding a conductor on of the notification appliance circuit.
Who is responsible for the inspection, testing, and maintenance of the alarm system?
Building owner. 14.6.1.3
Testing. Records
Additional manual fire alarm boxes shall be provided so that the travel distance to the nearest manual fire alarm Box will not exceed how many feet measured horizontally on the same floor?
200ft.
17.14 initiating devices. Manually actuated alarm initiating device