NFPA 17 (2013) Flashcards
Chapter 4 (Components)
At what temperature shall all devices be operating?
32°F to 120°F (0°C to 49°C)
Engineered and pre-engineered systems intended for the protection of total flooding applications that have unclosable openings with areas in excess of 1 percent of the total area exceeding 5% shall be compensated for the use of dry chemical no less than?
0.5/ft2 (cubic feet) 2.44kg
Where the unclosable openings have areas exceeding 5% of the total sides of enclosure and not exceeding 15%, compensated for the use of additional dry chemical no less than?
1lb/ft2 (4.88kg)
True or False: A fusible link or heat detector shall be provided above each protected cooking appliance and in accordance with the extinguishing system manufactures listing
True
True or False: Fusible links or heat detectors located at or within 8in into the exhaust duct opening and above the protected appliance shall be permitted to meet the requirements of 9.3.2.2
False (12in or 305mm)