NFPA 17 (2013) Flashcards

Chapter 4 (Components)

1
Q

At what temperature shall all devices be operating?

A

32°F to 120°F (0°C to 49°C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Engineered and pre-engineered systems intended for the protection of total flooding applications that have unclosable openings with areas in excess of 1 percent of the total area exceeding 5% shall be compensated for the use of dry chemical no less than?

A

0.5/ft2 (cubic feet) 2.44kg

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where the unclosable openings have areas exceeding 5% of the total sides of enclosure and not exceeding 15%, compensated for the use of additional dry chemical no less than?

A

1lb/ft2 (4.88kg)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

True or False: A fusible link or heat detector shall be provided above each protected cooking appliance and in accordance with the extinguishing system manufactures listing

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

True or False: Fusible links or heat detectors located at or within 8in into the exhaust duct opening and above the protected appliance shall be permitted to meet the requirements of 9.3.2.2

A

False (12in or 305mm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly