Nameplates Flashcards

0
Q

Station Service Transformer

A
Sorgel
3 phase 60 cycle
KVA - 1000
Class AA
Delta/Delta connected
HS - 13,800V 41.8A
LS - 480V 1200A
Impedance - 5.6%
Cont. duty rise - 80*C
Class B insulation
Type - SHT
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

Main Transformer

A
Westinghouse
3 phase 60 cycle
KVA - 43200/57600/72000
Class OA / FOA / FOA
Delta/Wye connected
HS - 69,000V 604A
LS - 13,200V 3,160A
Impedance 8.8% at OA Rating  
Cont. duty rise - 55*C
No load tap changer 
Tap #3 = 70,725V
Oil - 4900 gal
Class A insulation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Lighting Transformer

A
Hevi-duty Electric
3 phase 60 cycle
KVA - 150
Class AA-AFA
Delta/Wye connected
HS - 480V 180A
LS - 208/120V 416A
Impedance - 3.78 at AA rating 75*C
Cont. duty rise - 80*C
HS BIL - 10,000V
LS BIL - 10,000V
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Warehouse Transformer

A
Cutler-Hammer
3 phase 60 cycle
KVA - 750
Class AA
Delta/Delta connected
HS - 13,800V 31.4A
LS - 2,400V 180A
Impedance - 5.88%
Cont. duty rise - 115*C
HS BIL - 60,000V
LS BIL - 20,000V
Type - VPI
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

North bank Transformer 1

A
Balteav Standard Inc
3 phase 60 cycle
KVA - 500
Class OA
Delta/Wye connected
High side - 13,800V
Low side - 4160/2400V
Impedance - 4.87% @85*C
Continuous duty rise: 65*C
HS BIL - 95,000V
LS BIL - 60,000V
Oil - 160 gal
Class A insulation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

North bank Transformer 2

A
Niagra
3 phase 60 cycle
KVA - 500
Class OA
Delta/Wye connected
High side - 13,800V 20.92A
Low side - 4160/2400V
Impedance - 5.7% @85*C
Continuous duty rise: 65*C
HS BIL - 95,000V
LS BIL - 60,000V
Oil - 164 gal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Main Generator

A
GE AC generator
3 phase 60 cycle
KVA - 31,250
KW - 25,000
RPM - 75
Volts - 13,800V
Arm amp - 1,308
Field amp - 1,000
Power factor - 0.8
Excitation volts - 250
96 poles
60*C Arm by detection
60*C Field by resistance
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Main Exciter

A
GE DC generator
Type EVF
Shunt wound
KW - 300
RPM -75
Amps full load - 1,200
Volts full load - 250 
Volts no load - 0
Excitation volts - 250
10 Poles
Shunt field 40*C by thermometer - commutator 55*C
Ins. windings 40*C by thermometer - bare windings 50*C
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Pilot Exciter

A
GE DC generator
Type EV - self excited
Compound wound
KW - 17
RPM - 75
Amps full load - 68
Volts full load - 250
Volts no load - 250 
6 Poles
Shunt field 40*C by thermometer - commutator 55*C
Ins. windings 40*C by thermometer - bare windings 50*C
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Spillway Gate Motor and Gearbox

A
Louis Allis
Type FK
AC 3 phase 60 cycle
RPM - 1690
Volts - 440
Amps - 12.5
HP - 10
Cont duty rise - 50*C
Insulation - Class A
Splashproof
High speed
Foote Bros. Gear & Mach. Co.
Ratio  11.25:1
RPM - 1750 input
RPM - 155.5 output
Service HP - 13.1
Size, Type, Style - 6SA
Slow Speed
Western Gear Works
Ratio - 194.78:1
RPM - 152 pinion
HP - 4.7
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Neutral Reactor - current limiting reactor

A
Westinghouse
3 phase 60 cycle
Volts - 16,100
Amps - 2,000
165*C rise for 10 sec operation at rated amp
Oil - 156 gal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Deluge motor and pump

A
Lincoln	                       Aurora
AC 3 phase 60 cycle	  Centrifugal
HP - 60	                       GPM - 750
RPM - 1,775	                RPM - 1,775
Volts - 230/460	         Head - 196'
Amps - 154/77	
Class B insulation	
Rise - 40*C cont. duty	
Service factor - 1.15
How well did you know this?
1
Not at all
2
3
4
5
Perfectly