Annunciator Flashcards
Windows 1
Turbine Bearing High Temp
2 RTD - 70C
TBB11 - 85C
Foxboro - 55C
Foxboro - 55C - Oil return
Window 2
Turbine Bearing Oil Level Alarm
Foxboro - 1/8 Low 7/8 High
Window 3
DC Oil Pump Run
Motor Starter Contact 6QDC1
Windows 4
Turbine Bearing Low Oil Flow or Pressue
Teleflow Indicator @ 0 Flow
63Q1 - Mercoid - 5 PSI
Window 5
Gen. Upper Guide Brg. High Temp
2 RTD - 70C
TBB11 - 105C
Mercoid- 75C
Foxboro - 70C
Window 6
Gen. Upper Guide Brg. Oil Level
Magnetrol - High/Low
Window 7
Gen. Lower Guide Brg. High Temp.
2 RTD - 70C
TBB11 - 105C
Mercoid- 75C
Foxboro - 70C
Window 8
Gen. Bearing High Temp
4 RTD - 70C
TBB11 - 105C
Mercoid- 75C
Foxboro - 70C
2 RTD - 70C Oil
Foxboro - 55C Oil
Window 9
Gen. Thrust Brg. Oil Level Alarm
Magnetrol - High/Low
Window 10
Generator Brakes Applied
Pressure Switch off 20A1B @ 80 PSI
Window 11
Overspeed
Overspeed switch 12G1 @ 97.5 RPM, Resets 78.75 RPM
Window 12
Governor Oil Low Pressure
63Q1L - Pressure Switch @ 255 PSI
Window 13
Gov. Oil Pump Excessive Run Time
62QT Timer @ 3 mins
Window 14
95U Trouble
R6 output of the 95U, Self Check
Window 15
Head Cover Sump High Water
63S1B Mercoid/Float - High Level
DC Pump Run
Window 16
Kaplan Head Oil Level Alarm
Magnetrol/Float - High Level
Window 17
Kaplan Head High Temp.
3 - RTD - 70C
3- TBB11 - 105C
1 for each bushing
Window 18
Generator Air Coolers High Temp.
Foxboro - 45*C x 8
Window 19
Generator Air Coolers Low Water Flow
Toshiba Electromagnetic Flow Meter - 200 GPM or 25%
Window 20
Thrust Bearing Coolers Low Water Flow
Toshiba Electromagnetic Flow Meter - 30 GPM or 21.4%
Window 21
Stuffing Box Low Water Flow
Toshiba Electromagnetic Flow Meter - 4.3 or 43%
Window 22
Generator Stator High Temp
6 RTD - 100*C
Window 23
Gen. Field High Temp
Not Used
Window 24
Generator Diff. Relay Operation
87G1X (MG6) @ Operation of 95U R3
Window 25
Generator Ground Relay Operation
87G1X (MG6) @ Operation of 95U R3
Window 26
95U Alarm
R5 Output - 95U Operation
Window 27
Generator Overvoltage Relay Operation
59G1X (MG6) @ Operation of 59G1 (SV) @ 15.2 KV, reset at 14.8 KV
Window 28
440V Unit Bus No-Volt
Undervoltage Relay @ 0V
Window 29
Partial Shutdown Relay Operation
5P (WL) @ Operation of 51G1X or 87T1X
Window 30
Complete Shutdown Relay Operation
5C (WL) @ Operation of 5A1, 1G11, 1G12, 64G1, 87G1X2, 63Q1CX, CO2 Pressure Switch 1PS2
Window 31
Generator C02 Release
87G1X initiated by R3 on 95U
Window 32
Unit Available For Operation
Fisherman Warning System Timeout After Condensing