Annunciator Flashcards

1
Q

Windows 1

A

Turbine Bearing High Temp

2 RTD - 70C
TBB11 - 85
C
Foxboro - 55C
Foxboro - 55
C - Oil return

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Window 2

A

Turbine Bearing Oil Level Alarm

Foxboro - 1/8 Low 7/8 High

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Window 3

A

DC Oil Pump Run

Motor Starter Contact 6QDC1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Windows 4

A

Turbine Bearing Low Oil Flow or Pressue

Teleflow Indicator @ 0 Flow
63Q1 - Mercoid - 5 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Window 5

A

Gen. Upper Guide Brg. High Temp

2 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Window 6

A

Gen. Upper Guide Brg. Oil Level

Magnetrol - High/Low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Window 7

A

Gen. Lower Guide Brg. High Temp.

2 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Window 8

A

Gen. Bearing High Temp

4 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

2 RTD - 70C Oil
Foxboro - 55
C Oil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Window 9

A

Gen. Thrust Brg. Oil Level Alarm

Magnetrol - High/Low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Window 10

A

Generator Brakes Applied

Pressure Switch off 20A1B @ 80 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Window 11

A

Overspeed

Overspeed switch 12G1 @ 97.5 RPM, Resets 78.75 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Window 12

A

Governor Oil Low Pressure

63Q1L - Pressure Switch @ 255 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Window 13

A

Gov. Oil Pump Excessive Run Time

62QT Timer @ 3 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Window 14

A

95U Trouble

R6 output of the 95U, Self Check

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Window 15

A

Head Cover Sump High Water

63S1B Mercoid/Float - High Level
DC Pump Run

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Window 16

A

Kaplan Head Oil Level Alarm

Magnetrol/Float - High Level

17
Q

Window 17

A

Kaplan Head High Temp.

3 - RTD - 70C
3- TBB11 - 105
C
1 for each bushing

18
Q

Window 18

A

Generator Air Coolers High Temp.

Foxboro - 45*C x 8

19
Q

Window 19

A

Generator Air Coolers Low Water Flow

Toshiba Electromagnetic Flow Meter - 200 GPM or 25%

20
Q

Window 20

A

Thrust Bearing Coolers Low Water Flow

Toshiba Electromagnetic Flow Meter - 30 GPM or 21.4%

21
Q

Window 21

A

Stuffing Box Low Water Flow

Toshiba Electromagnetic Flow Meter - 4.3 or 43%

22
Q

Window 22

A

Generator Stator High Temp

6 RTD - 100*C

23
Q

Window 23

A

Gen. Field High Temp

Not Used

24
Q

Window 24

A

Generator Diff. Relay Operation

87G1X (MG6) @ Operation of 95U R3

25
Q

Window 25

A

Generator Ground Relay Operation

87G1X (MG6) @ Operation of 95U R3

26
Q

Window 26

A

95U Alarm

R5 Output - 95U Operation

27
Q

Window 27

A

Generator Overvoltage Relay Operation

59G1X (MG6) @ Operation of 59G1 (SV) @ 15.2 KV, reset at 14.8 KV

28
Q

Window 28

A

440V Unit Bus No-Volt

Undervoltage Relay @ 0V

29
Q

Window 29

A

Partial Shutdown Relay Operation

5P (WL) @ Operation of 51G1X or 87T1X

30
Q

Window 30

A

Complete Shutdown Relay Operation

5C (WL) @ Operation of 5A1, 1G11, 1G12, 64G1, 87G1X2, 63Q1CX, CO2 Pressure Switch 1PS2

31
Q

Window 31

A

Generator C02 Release

87G1X initiated by R3 on 95U

32
Q

Window 32

A

Unit Available For Operation

Fisherman Warning System Timeout After Condensing