What is the EHC system mainly controlling?

A

Reactor pressure to control reactivity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens if turbine limit (setpoint) is exceeded?

A

Bypass valves open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens if EHC pump ‘B’ < 1600 psig @ >26% power?

A

Turbine trip and reactor SCRAM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

how many overspeed protection systems are required?

A

Both of them:

DOPS and back-up overspeed (ovation)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many bypass valves are there?

A

3 bypass valve.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How much can bypass valves bypass?

A

30%, (10% each valve)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many bypass valves are required? why?

A

2 required

thermal limit penalty imposed by MCPR and LHGR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many stop and control valves are required?

A

ALL of them

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If EHC is ingested, what should be done?

A

induce vomiting

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What PPE should be used when around EHC fluid?

A

Glove, face shield, respirator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What type of respirator should be used when handling EHC fluid?

A

Air purifying

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What level should not be exceeded when filling EHC reservoir? why?

A

34” to prevent overfilling tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

when will the standby EHC pump auto-start?

A

<1800 psig on running pump OR header if pump is in Auto-STBY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the EHC pump trips?

A

< 15” EHC tank level LO-LO

MPD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the heater start permissives?

A

> 15” tank level

Recirc pump must be running

< 105 deg F heater start

> 115 deg F heater stop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When will the main turbine trip relative to EHC pressure

A

<1600 psig

17
Q

What does the cornsilk color mean?

A

it is selected

18
Q

When does the high filter DP alarm come in?

A

> 72 psid

19
Q

What’s the primary purpose of the stop valves?

A

prevent overspeed of turbine on turbine trip

20
Q

on a turbine trip, what controls Rx pressure?

A

Bypass valves

21
Q

What must be done for a setpoint to be active?

A

Enable or confirm it

22
Q

How do control/bypass/stop valves operate?

A

Fluid to open, spring to close

23
Q

what valves are fast close, and which are fast opening?

A

Fast close – stop and control valves

Fast opening – bypass valves

24
Q

What’s the power supply to EHC pumps?

A

A - 13AD

B - 14AE

25
Q

What’s the power supply to Ovation?

and control power?

A

Inverter power 120 VAC (BOP)

26
Q

What’s the tech spec part of EHC? (safety function)

A

BYPASS VALVES

27
Q

What cools EHC

A

TBCW

28
Q

How does the Temp control valve fail?

A

OPEN (max cooling)

29
Q

What needs to be running to run the EHC heater?

A

Recirc pumps

30
Q

What temp does the heater maintain?

A

105 - 115 deg F

31
Q

What the SCRAM setpoints? (EOC RPT) and (EHC pressure)

A

TSV < 675 psig

TCV < 970 psig

<1600 psig header pressure

32
Q

When are the SCRAM setpoints bypassed?

A

< 26% Rx power

33
Q

What type of SCRAM is the EHC scram?

A

RPS scram

34
Q

What is temp maintained at when running by temp control valve?

A

115 - 130 deg F