C41 - SLC Flashcards
How is SLC initiated?
No automatic initiation (manual with control room key switches)
Where does SLC enter the Rx?
through HPCS sparger
What’s the tech spec limit for the SLC tank level?
4,200 gallons
What’s the flow rate of SLC pumps?
41.2 gpm per pump @ 1370 psig
Ho does a squib valve operate?
Leak tight explosive valve that provides highly reliable way to test SLC system at a high pressure without leakage into the Rx.
Where are the SLC storage tank heaters controlled from?
Locally with handswitch
What are the power supplies to the SLC suction valves, squib valves, and pumps?
A - 15
B - 16
How are the suction valves operated?
Local handswitch or on initiation
When will the suction valves not auto open on initiation?
why?
When test tank outlet valve F031 is not fully closed
this is to prevent inadvertent contamination of SLC test tank with sodium pentaborate from storage tank
What does service air do for SLC?
Goes through spargers for agitation and MIXING chemical or when required for sampling
What does instrument air do for SLC?
Admits air into flow indicator for level indication (bubbler system)
Describe the initiation of SLC system
- Squib valves fire
- F001 A/B (suction valves) open
- Isolates RWCU ‘A’ pump G33-F004 close
‘B’ pump and G33-F001 and G33-F251 close
Pump starts (All previous actions happen simultaneously. When suction valve is full open, then pump starts) *if test tank outlet valve F031 is not full closed, suction will not auto open*