Modern Refrigeration 21st Edition Flashcards
Your customer has an existing attic with a U-factor of .04. R-30 has been added to the attic so the new U-factor of the ceiling is?
.018
R = 1 ÷ U-factor
R = 1 ÷ .04
R = 25
R25 + R30 = R55
U-factor = 1 ÷ R-Value U-factor = 1 ÷ 55 U-factor = .018
Pg. 1315 Modern Refrigeration
The term __________ indicates that a portion of the liquid refrigerant in circulation that turns into a vapor as it passes through the refrigerant control device.
Flash Gas
Glossary Modern Refrigeration
When trying to reduce vibration from a commercial compressor, vibration isolators should be installed. How many vibration isolators should be installed in each line when you have horizontal and vertical vibration?
2 in each line
Pg. 1371 and Pg. 462 Modern Refrigeration
An externally equalized thermostatic expansion valve should always be used when the pressure drop across the evaporator coil exceeds ________psi.
4psi
Pg. 479 Modern Refrigeration
How many British Thermal Units does it take to melt 2,000lbs of ice in a 24 hour period?
12,000BTU
Pg. 66 Modern Refrigeration
What is the critical temperature of R-410A Refrigerant?
72.1⁰C
Pg. 1502 Modern Refrigeration
When servicing disposable filters in HVAC systems, the filter must be replaced when the pressure drop across the filter exceeds ______% of the pressure drop across the fan.
25%
Pg. 771 Modern Refrigeration
An air conditioning installation has a vibration in the refrigerant lines that is being transmitted to the structure. Suitable vibration isolators have been installed. What other option would help eliminate the line vibration?
A horizontal loop of soft copper in the suction line and a vertical loop in the liquid line.
Pg. 462 and Pg. 1372 Modern Refrigeration
Refrigerant at a temperature below it’s saturated temperature is said to be?
Subcooled
Pg. 1570 Modern Refrigeration
The boiling point of water is ________⁰C
100⁰C
Pg. 58 Modern Refrigeration
A/An _________ is the component in a heat pump that changes liquid refrigerant into a vapor when heat is absorbed into the system in the heating cycle.
Outdoor coil.
Pg. 1050 Modern Refrigeration