What is the minimum width of the required continuous solid flooring along the required access path to an attic appliance?
22 inches
Pg. 22 Mechanical Code
When smoke detectors are required by code, they shall be installed based on what?
NFPA 72
Pg. 74 Mechanical Code
When running PVC pipe underground for use as part of a domestic kitchen exhaust system, no more than _________ inches of PVC duct is allowed to extend above the concrete floor.
1 in
Pg. 49 Mechanical Code
When installing a duct heater with heat pumps or air conditioners, the maximum distance the heater can be from the air handling unit is?
4ft.
Pg. 93 Mechanical Code
Appliances requiring service are located on a flat foot that is 16ft above grade. There is also a 4ft parapet that hides the equipment from view from the street. Is a permanent means of access required for servicing the equipment?
Yes
Pg. 22 Mechanical Code
A domestic clothes dryer termination leaves the building and terminates less that 12in from the adjoining grade. It is impossible to relocate the wall cap, what can be done to meet code?
Dig a 200sq.in. area well under the wall cap.
Pg. 48 Mechanical Code
You are replacing a 10T rooftop package unit in a small commercial building. To ensure the system is properly sized, you want to run a load calculation. What load estimating procedure should you use for this building according to code?
ASHRAE/ACCA Standard 183
Pg. 26 Mechanical Code
You are installing a medium duty kitchen hood in a commercial application. The hood type is a single island canopy hood. The hood is 10ft long. How may CFM of total exhaust air will be required?
5000cfm
Pg. 56 Mechanical Code
500cfm per linear foot
Length=10ft
500 x 10= 5000cfm
Under what condition can UL listed and labeled Class 1 flexible air duct pass through a fire resistance rated assembly?
Never
Pg. 79 Mechanical Code
An electric resistance duct heater is installed in sheet metal ductwork that is lined with 1in of ASTM E-84 rated duct insulation. What is the installation requirement for the liner near the duct heater?
Interrupt liner 6in before and 6in after the heater.
Pg. 73 Mechanical Code
A bowling alley seating area is 3000sqft of the total buildings 18,000sqft. The seating area requires a minimum of ______ cubic feet of outside air per minute per the code based on the estimated occupant load and cfm per person.
1200cfm
Pg. 31, 36 Mechanical Code
Occupant density= 40(people) per 1000sqft Outdoor Airflow Rate= 10cfm per person 40/1000 = x/3000 x=120 120 people
OAR= 120people x 10cfm per person
Outdoor Airflow Rate= 1200cfm
The minimum size of an oil supply line feeding an oil fired appliance shall be at least ______
3/8in
Pg. 120 Mechanical Code
You are installing an oil burning furnace in a residential application. The Furnace has a flame retention burner rated at a maximum capacity of 120,000 btu/hr. What is the minimum gage of the vent connector material if it is constructed of galvanized steel?
28 gage
Pg. 85 Mechanical Code
A small coffee shop serves sandwiches and other lightly prepared food and uses 6 commercial microwaves and 3 light duty electric convection ovens. Is a Type 1 Hood required for this application?
No
Pg. 55 Mechanical Code
When installing PVC pipe in concrete for down draft domestic kitchen exhaust duct, the PVC pipe shall not extend more than ______ above the concrete floor indoors.
1in
Pg. 49 Mechanical Code