Mechanical Final Heat Exchangers & MD Review Flashcards
An AXV works best when the evaporator load is constant.
True
The pin or valve port piston of the electronic step-motor expansion valve can move a linear motion of 300 steps per second.
False
A refrigeration system that continuously runs under high-load conditions (hot pull downs) would most likely use a thermostatic expansion valve with a vapor charged thermal bulb assembly.
True
Too high of pressure entering the compressor will cause the density of suction gases entering the compressor to increase.
True
To check the performance of a dry-type evaporator, the service technician would first make sure that the refrigerant coil is operating with enough liquid inside.
True
When condensation cannot flow directly to a drain, a condensate pump can be used to move it to the drain.
True
Some commercial refrigeration applications require that water be kept from freezing at temperatures below 32°F (0°C).
True
A PWM solenoid EEV can hold its valve at any variable position between open and closed for the purpose of modulating refrigerant flow.
False
Adsorption occurs when two substances combine to become one substance.
False
In a heat pump system with two piston-type fixed-orifice metering devices, one piston meters refrigerant flowing in one direction and allows free flow in the other direction.
True
The purpose of a capillary tube is to ____.
regulate the refrigerant flow into the evaporator
lower the pressure of the liquid refrigerant
lower the boiling point of the refrigerant
all of the above
d) all of the above
The pressure limiting TXV ____.
allows the compressor to operate at low condenser entering air temperatures
shuts off the condenser fan during hot pull down
maintains the full refrigerant flow rate during a hot pull down
limits the refrigerant flow rate to the compressor capacity
d) limits the refrigerant flow rate to the compressor capacity
Balanced port TXVs are used to ____.
feed refrigerant at a normal rate with low condenser entering air temperatures
feed refrigerant at a normal rate with high condenser entering air temperatures
stop refrigerant flow with high condenser entering air temperatures
stop refrigerant flow with low condenser entering air temperatures
a) feed refrigerant at a normal rate with low condenser entering air temperatures
When the load on the evaporator increases, the TXV ____.
increases the flow of refrigerant
decreases the flow of refrigerant
maintains constant head pressure
decreases the pressure drop across the evaporator
a) increases the flow of refrigerant
The cross liquid charge bulb at the TXV contains fluid that ____.
has similar characteristics to the system fluid to prevent liquid refrigerant from entering the suction line
has different characteristics from the system fluid
causes the valve to stay open during the off cycle
follows the typical pressure-temperature relationship
b) has different characteristics from the system fluid
If a thermostatic expansion valve’s thermal bulb came loose from the suction line at the outlet of the evaporator, which of the following could result?
The bulb pressure would increase and the thermostatic expansion valve would open.
The superheat in the evaporator would decrease.
Liquid refrigerant would flow back to the compressor.
All of the above are correct.
d) all of the above answers are correct
A thermostatic expansion valve controls refrigerant flow to the evaporator based on ____.
rate of liquid vaporization
evaporator suction line superheat
external equalizer pressure
all of the above
b) evaporator suction line superheat
The primary function of an expansion device is to ____.
produce a reduction in the pressure on the liquid refrigerant
regulate the flow of refrigerant into the evaporator
lower the boiling point of the refrigerant far enough below the temperature of the load to get the needed heat transfer rate
all of the above
d) all of the above
Which of the following can be used to maintain the head pressure of a system with an air-cooled condenser?
fan cycling
condenser flooding valve
dampers or louvers
all of the above
d) all of the above
An air-cooled condenser that is operating in a climate that has four distinct seasons must ____.
have some type of head pressure control
use a water regulating valve
have a multi-circuit evaporator
operate with zero degrees of subcooling
a) have some type of head pressure control
Condensing temperatures in an air-cooled condensing unit can be reduced by ____.
increasing the condensing surface area
increasing the cfm through the condenser
decreasing the temperature of the air entering the condenser
all of the above
d) all of the above
If an R-12 refrigeration system has its air-cooled condensing unit on a 100°F roof and the condenser outlet temperature (refrigerant) is 115°F, with how much subcooling is the condenser operating?
30°F
15°F
100°F
130°F
b) 15F
A normally operating water-cooled condenser is operating with a 10° differential between water in and water out. If the amount of 85°F water going through the condenser is reduced, which of the following is a possible temperature of the water leaving the condenser?
75°F
0°F
95°F
105°F
d) 105F
What can be used to maintain the head pressure of a system with a water-cooled condenser?
fan cycling
dampers or louvers
water regulating valve
all of the above
c) water regulating valve
In a water-cooled condenser, a regulating valve is used to control the ____.
refrigerant flow through the pressure reducing device
refrigerant condensing temperature
suction pressure
water temperature
b) refrigerant condensing temperature
The shell-and-tube condenser is cleaned ____.
with a brush after removing the end caps
only with chemicals
with compressed air
with a vacuum cleaner
a) with a brush after removing the end caps
The water circuit in shell and coil and coil-type tube-in-a-tube condensers must be cleaned ____.
by removing the end caps
with a brush
chemically
by air pressure
c) chemically
In a water-cooled condenser with dirty condenser tubes, the temperature difference between the refrigerant and the leaving water will be ____ when the tubes are clean.
less than
greater than
the same as
slightly lower than
greater than
Mineral deposits in the water portion of a water-cooled condenser act as ____.
a conductor of heat
an insulator
a cleaning solution
They have no effect on the operation of the condenser.
an insulator
A normally operating water-cooled condenser is operating with a 10° differential between water in and water out. If scale forms on the water tubes and the entering water is 85°F, which of the following is possible?
The outlet water temperature will be lower than expected.
The system head pressure will rise.
The water regulating valve will close.
Both a and b are correct.
Both A and B are correct
The condenser in a refrigeration system ____.
desuperheats the vapor from the compressor
condenses the vapor from the compressor
subcools the liquid refrigerant before it leaves the condenser
all of the above
all of the above
The refrigerant in a condenser in a refrigeration system ____.
absorbs heat
rejects heat
changes to a vapor
is under lower pressure than the evaporator
rejects heat
A typical superheat for an evaporator operating under normal conditions would be ____.
4 to 6°F
6 to 8°F
8 to 12°F
14 to 16°F
8 to 12F