Main Generator Flashcards
Generator Limitations
Air Cooled (5#) - 126,000 (.88pf) KVA (120,000 (.85) KVA
No SWC Flow (1hr Limit) - 240,000 KVA w/60# H2
One H2 Cooler OOS - 800,000 KVA
1/2 H2 Cooler OOS - Full load with air temp 86-118degF
One SWC Cooler OOS - 924,000 KVA w/PSW <85degF & >3200gpm
Iso-phase cooling lost - 14,000 (12,800) Amps
Self-Cooled - 6466 Amps
Shaft Voltage Monitor
Prevents damage to bearings due to build up of static electricity onto rotating element
How EX2100 transmits voltage to the armature (Rotor)
Brushes and collector rings
Generator Trips
Generator Faults (Differential and Neutral Overcurrent Main Transformer Fault Aux Transformer Fault Generator overload Generator underfrequency 59.4 - 180 Seconds 57.9Hz for 110 Seconds 57.4Hz for 15 Seconds 56.9Hz for 2.4 Seconds
Sequential vs Simultaneous Trip
Sequential trips – TSV close steam is exhausted and PCBs open on reverse power (3.75sec) and exciter stops.
Synchronous trips, all things happen together….
Max System Voltages
Generator output is 24KV
230 and 500KV max is 104.9% and min is 101.3% of rated
Generator Runback
Must be < 20,232 Amps in 2 mins
Must be < 6466 Amps in 3.5 mins
Purpose of EX2100
PPT converts 800VAC to 125DC for field excitation
Operation of disconnects
Rubber Gloves, Rubber Boots, Hard Hat, Safety Glasses, and Flame Resistant or Cotton Clothes