Limits Flashcards
NOx Limits
0.09 lb/MBTU 24 hr average
SO2 Limits
0.16 lb/MBTU 3hr average
CO Limits
1003 lb/hr 30day average
Slag conditions >150ppm
Hg Limits
1.2 lb/TBTU 30 day average
Opacity Limits
10% 6min average
Reheat protection
Total fuel >20% with turbine not in service
Furnace pressure Limits
+/- 12inches of water
Drum level Limits
+11.25” / -10”
Total Air Limits
< 28.7% unit trip
43% minimum in auto
35% for purge
DAST lvl
100” set point
> 136” turbine trip
118” dump valve opens
< 12” Both BFPs trip
RAH outlet temp Limits
> 350F on 2of3 probes on either RAH trips the plant.
Slaking Temp
Normal set point 180F
not to exceed 100degree rise from inlet temp.
High Temp trip 195F
Warming cycle required <120F
Dilution water tank Limits
Set point 160”
High level cut off 172”
Pump trip 48”
Condenser hotwell Limits
High alarm 37”
Set point 32”
Pump trip 15”
Cooling Tower basin Limits
Set point 225”
High 234” (shuts fill valve)
240” overflow
200” point of accelerating concern
172” Pumps trip => unit trip