Every portion of any assembly building which contains seats, tables, displays, equipment, or other materials shall be provided with aisles leading to an exit. When serving sixty (60) seats or less, aisles shall
be not less than seven hundred sixty millimeters (760 mm) wide
The occupant load of educational buildings or any individual storey or section thereof for the purpose of determining exits shall not be less than one (1) person for each __________ of net classroom area or _______ of net area of shops, laboratories, and similar vocational rooms.
one and nine tenths square meters; four and six tenths square meters
Fire extinguishers shall be selected for the classes of hazards to be protected. Fire extinguishers for protection of Class B hazard shall be selected from the following except:
Multipurpose dry chemical type
Portable fire extinguishers are classified for use on certain classes of fires and rated for relative extinguishing effectiveness as determined by the Bureau of Product Standard, Department of Trade and Industry (DTI). What is the classification of fires involving combustible metal fires?
Class D
Under Rule 10 Chapter 2 Division 5 of RA 9514 and its RIRR, an exit shall consist of the approved components that are described, regulated, and limited as to use by _______________ of this RIRR.
Sections 10.2.5.3 through 10.2.5.13
Portable fire extinguishers are classified for use on certain classes of fires and rated for relative extinguishing effectiveness as determined by the Bureau of Product Standard, Department of Trade and Industry (DTI). What is the classification of fires involving energized electrical equipment?
Class C
Portable fire extinguishers are classified for use on certain classes of fires and rated for relative extinguishing effectiveness as determined by the Bureau of Product Standard, Department of Trade and Industry (DTI). What is the classification of fires involving flammable and combustible liquid and gas?
Class B
Classification of Occupancy: refers to two (2) or more classes of occupancies occurring/located/situated/existing in the same building
Mixed Occupancies
As provided in Divisions 8 through 20 of Chapter 2, activation of the complete fire alarm system shall be initiated by, but not be limited to, any or all of the following means:
Manual initiation
Automatic detection
Extinguishing system operation
What is the width of a stair having a total cumulative occupant load of less than 2000 persons?
1120 mm
According to Rule 10 Chapter 2 Division 2 of the RA 9514 and its RIRR, who will take the initiative of formulating the fire safety program for his/her building and of organizing the occupants to implement the programs?
The building owner
Classification of Hazard of Contents: Those which are liable to burn with extreme rapidity or from which poisonous gases or explosions are to be expected in the event of fire.
High Hazard
What is the maximum height of risers for new stairs
180 mm
Classification of Occupancy: Internet shops of over fifty (50) persons capacity.
Assembly
Every exit shall have the word “EXIT” in plainly legible letters not less than __________ in height, with the principal strokes of letters not less than nineteen millimeters (19 mm) in width.
one hundred fifty millimeters
A room whose only means of egress is through an adjoining or intervening room, which is not an exit.
Interior Room