[L9]_Ductwork Sizing & Design Flashcards
IND405
What is the goal of an air distribution system?
[L9]
Provide thermal comfort and ventilation for people in a space.
[L9]
IND405
What are the three (3) categories of Space Air Diffusion?
[L9]
- Fully (thermally) Stratified Systems
- Partially Mixed Systems
- Fully Mixed Systems
[L9]
IND405
Is this example room Fully Stratified or Mixed?
[L9]
Fully Stratified Room
[L9]
IND405
What are the three (3) example fans used for thermal destratification?
[L9]
- HTHV (High-Temperature Heating & Ventilation) Fan
- Large Circulation Fan
- Compact Jet Stream Fan
[L9]
IND405
What type of air-flow jet stream is shown in the image below?
[L9]
Isothermal Jet Stream, the temperature of the jet stream is the same as the proposed space.
[L9]
IND405
True or False: Non-isothermal jet streams have the same starting temperature different from the ambient air.
[L9]
False. The starting temperature for a non-isothermal jet stream is different.
[L9]
IND405
How many Diffuser Outlet Group Classifications are there?
[L9]
There are five (5) outlet diffuser group classifications.
[L9]
IND405
What diffuser outlet group is in the sample photo?
[L9]
Group A: Diffusers mounted in or near the ceiling that discharge air horizontally.
[L9]
IND405
What diffuser outlet group is in the sample photo?
[L9]
Group C: Diffusers mounted in or near the floor that discharge air vertically in a spreading jet.
[L9]
IND405
What diffuser outlet group is in the sample photo?
[L9]
Group E: Diffusers mounted in or near the ceiling that project air vertically down.
[L9]
IND405
Name four (4) main components of air distribution systems.
[L9]
- Ductwork
- Diffusers
- Dampers
- Insulation Wrapping & Lining
[L9]
IND405
What is the typical galvanized steel ductwork thickness used for low pressure systems?
[L9]
22-gauge galvanized steel
[L9]
IND405
Mastic Sealant is used for what type of ductwork systems?
[L9]
Medium & High Pressure Ductwork Systems
[L9]
IND405
Gasket Clamp systems are used for what type of ductwork systems?
[L9]
Combustion Flue or Chimeny Ductwork Systems.
[L9]
IND405
List the six (6) required ductwork layout distribution design considerations.
[L9]
- Space Availability
- Installation Cost
- Air Friction Loss
- Noise Level
- Duct Heat Transfer & Leakage
- SMACNA Ductwork Construction Standards
[L9]
IND405
What does SMACNA stand for?
[L9]
Sheet Metal and Air-Conditioning Contractors’ National Association
[L9]
IND405
What type of ductwork layout is shown in this example?
[L9]
Core & Shell, Trunk & Branch Layout
[L9]
IND405
What are the three (3) types of duct sizing methods?
[L9]
- Static Pressure Recovery Method (Static Regain Method)
- Velocity Method
- Constant Pressure Method aka (Equal Friction Method)
[L9]
IND405
Which duct sizing method is the most complicated that is almost always only performed by computer?
[L9]
Static Pressure Recovery Method (Static Regain Method)
[L9]
IND405
Define the Velocity duct sizing method.
[L9]
Velocity Method is based on the fan discharge speed to provide progressively lower duct velocities as the air proceeds from the main duct to the branches and outlets.
[L9]
IND405
What are the two (2) design requirements when using velocity ductwork sizing method?
[L9]
- Application for Use Space Occupancy
- Noise Criteria for designated Use Space Occupancy
[L9]
IND405
Name five (5) different types of dampers for a ductwork system?
[L9]
- Gravity Damper
- Volume Damper
- Motorized Damper
- Smoke Damper
- Fire Damper
[L9]
IND405
What is the recommended maximum air velocity (FPM) for space “Above Suspended Acoustical Ceiling” @ 25 NC level?
[L9]
1,200 FPM
[L9]
IND405
What are the two (2) types of pressure required to calculate to ductwork total pressure?
[L9]
Static Pressure & Velocity Pressure
[L9]
IND405
What is the formula for ductwork Dynamic Pressure?
[L9]
Pv = [Density * (Velocity^2)]/2
or
Pv = (V/4005)^2
[L9]
IND405
List the static pressure ranges for the following duct systems.
* Low-Pressure Ductwork System
* Medium-Pressure Ductwork System
* High-Pressure Ductwork System
[L9]
- Low-Pressure Ductwork System: <=2-in. w.c.
- Medium-Pressure Ductwork System: > 2-in. w.c. and <= 3-in. w.c.
- High-Pressure Ductwork System: > 3-in. w.c.
[L9]
IND405
What is the base ductwork shape started with then converted depending on the shape of the ductwork you want for your design?
[L9]
You will always start with a ROUND ductwork sqft area equivalent to then change to RECTANGULAR or OVAL systems.
[L9]
IND405
What is the ratio that must be maintained for rectangular ductwork?
[L9]
Rectangular Duct Aspect Ratio is 4:1
[L9]
IND405
True or False: The Equal Friction method creates an automatic velocity reduction through the system.
[L9]
True.
[L9]
IND405
What is the typical equal friction loss pressure drop assumed for low-pressure ductwork systems?
[L9]
0.1-in.w.g./100-FT
[L9]
IND405
When calculating ductwork using the Equal Friction Method what are the three (3) component pressure loss categories you must calculate?
[L9]
- Straight Duct Losses
- Duct Fitting Losses
- Accessories Losses
[L9]
IND405
What manual do you reference to find all ductwork fitting pressure losses when sizing a system?
[L9]
SMACNA HVAC Duct System Design Manual
[L9]
IND405
What type of diffuser is shown in the image?
[L9]
2’x2’ Square Ceiling Drop ACT Diffuser
[L9]
IND405
What type of diffuser is shown in the image?
[L9]
Four (4) Slot Architectural Linear Diffuser
[L9]
IND405
What is the typical insturment used to measure actual air-flow from a supply diffuser?
[L9]
Anemometer
[L9]
IND405
What type of diffuser is shown in the image?
[L9]
Single-deflection side wall supply grille
[L9]
IND405
What is the HVAC ductwork component shown in the image?
[L9]
Motorized Opposed Blade Damper
[L9]
IND405
Which company manufactures the most prevalent motorized damper actuator utilized in the HVAC industry?
[L9]
Belimo
[L9]
IND405
Given an elbow fitting with a loss coefficient K of 0.75 and an airflow velocity of 900 feet per minute (FPM), calculate the pressure loss (ΔP) in the fitting. Use the following formula:
ΔP = 0.5 × ρ × V^2 ×K
[L9]
ΔP = 0.5 × 0.075lb/ft^3 × (900/60)^2-ft/s^2 × 0.75
ΔP = 0.5 × 0.075 × 225 × 0.75
ΔP ≈ 8.44-inches wc.
[L9]
IND405
A straight duct has a fitting with a coefficient C of 0.35. If the airflow velocity in the duct is 800-FPM, calculate the total pressure loss (TP) using the formulas:
Vp = 0.5 × ρ × V^2
&
TP = C x Vp
[L9]
First, calculate Vp:
Vp = 0.5 × 0.075-lb/ft^3 × (800/60)^2-ft/s^2
Vp = 0.5 × 0.075 x 177.78
Vp ≈ 6.67-inches wc.
Then calculate the TP:
TP = 0.35 × 6.67
TP ≈ 2.33-inches wc.
[L9]