[L12]_HVAC Hydronic Cooling System Flashcards

1
Q

IND405

Increasing the ∆t of chilled water from 8°F to 12°F results in which of the following benefits?
A. Reduced circulating pump horsepower by 50%
B. Increased chiller efficiency and reduced GPM by 33%
C. Higher system pressure losses
D. No significant changes

[L12]

A

B. Increased chiller efficiency and reduced GPM by 33%

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

IND405

True/False: Chilled-water systems must avoid temperatures below 32°F to prevent reservoir water freezing.

[L12]

A

True

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

IND405

Match the chiller type with its characteristic:
1. Air-Cooled Chillers
2. Water-Cooled Electric Chillers
3. Water-Cooled Absorption Chillers

A. Requires high-pressure steam or natural gas as energy source
B. Typically located outdoors with harsh environmental exposure
C. Offers long life expectancy and is ideal for substantial cooling loads

[L12]

A

1 = B. Typically located outdoors with harsh environmental exposure
2 = C. Offers long life expectancy and is ideal for substantial cooling loads
3 = A. Requires high-pressure steam or natural gas as energy source

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

IND405

Which type of chiller has the highest part-load efficiency?
A. Water-Cooled Steam Turbine Chiller
B. Water-Cooled Electric Chiller with Magnetic Bearings
C. Air-Cooled Chiller
D. Single-Stage Absorption Chiller

[L12]

A

B. Water-Cooled Electric Chiller with Magnetic Bearings

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

IND405

True/False: Water-cooled chillers are generally more energy efficient than air-cooled chillers.

[L12]

A

True

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

IND405

Which dual-temperature system offers the most flexibility for simultaneous heating and cooling?
A. Two-Pipe System
B. Four-Pipe Independent System
C. Four-Pipe Common System
D. Single-Pipe System

[L12]

A

B. Four-Pipe Independent System

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

IND405

A control valve is needed for a 30-Ton cooling coil with a 12°F ∆t and a pressure drop of 5 psi. What is the required Cv of the valve?

[L12]

A

Cv = 26.83

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

IND405

Antifreeze solutions in chilled-water systems does not help prevent freezing but can cause corrosion if inhibitors are not used.

[L12]

A

False

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

IND405

What is the typical chilled-water flow rate per ton of cooling?
A. 0.5 GPM
B. 1-1.5 GPM
C. 2-2.5 GPM
D. 3-4 GPM

[L12]

A

B. 1-1.5 GPM

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

IND405

True/False: Pressure loss correction is unnecessary for glycol solutions above 160°F.

[L12]

A

True

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

IND405

Match the air elimination type with its function:
1. Air Separator
2. Manual Vent
3. Automatic Air Removal Device

A. Removes trapped air at high points in the system
B. Installed at points of lowest solubility to remove air continuously
C. Provides servicing capability without system drainage

[L12]

A

1 = B. Installed at points of lowest solubility to remove air continuously
2 = A. Removes trapped air at high points in the system
3 = C. Provides servicing capability without system drainage

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

IND405

Ethylene glycol solutions can increase system viscosity, potentially reducing pump efficiency.

[L12]

A

True

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

IND405

What is recommended to preserve the life of a system using antifreeze solutions?
A. Flush the system with hard water before injecting glycol.
B. Use waters low in chloride and sulfate ions to prepare the solution.
C. Limit operating temperatures to below 120°F.
D. Avoid cleaning and flushing the system.

[L12]

A

B. Use waters low in chloride and sulfate ions to prepare the solution.

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

IND405

True/False: A diaphragm tank is required in chilled-water systems to control air and pressure fluctuations.

[L12]

A

True

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

IND405

A chilled-water system has a total head loss of 95-ft, a flow rate of 400-GPM, and a pump efficiency of 75%. What is the required pump horsepower?

[L12]

A

HP = 12.79 ≈ 15 HP

[L12]

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

IND405

What is the purpose of balancing valves on the return side of a chilled-water coil?
A. To act as a shut-off valve
B. To regulate and measure flow rates
C. To increase the velocity of water
D. To cool down overheated water

[L12]

A

B. To regulate and measure flow rates

[L12]

17
Q

IND405

True/False: A two-pipe dual-temperature system is suitable for buildings requiring simultaneous heating and cooling.

[L12]

A

False

[L12]

18
Q

IND405

Match the freeze protection measure with its purpose:
1. Low-temperature thermostats
2. Antifreeze solutions
3. Full-open valve position

A. Keeps water flowing in coils during dormant periods
B. Detects freezing temperatures and prevents coil damage
C. Prevents water from freezing in piping and coils

[L12]

A

1 = B. Detects freezing temperatures and prevents coil damage
2 = C. Prevents water from freezing in piping and coils
3 = A. Keeps water flowing in coils during dormant periods

[L12]

19
Q

IND405

True/False: Water-cooled absorption chillers are more efficient than electric chillers at both full and part load.

[L12]

A

False

[L12]

20
Q

IND405

Which of the following is NOT a primary purpose of pipe insulation in chilled-water systems?
A. Reduce heat loss
B. Prevent condensation
C. Increase water velocity
D. Protect against pipe sweating

[L12]

A

C. Increase water velocity

[L12]