L1 - General Rules - Part 2 Flashcards
Generally, is substitution of electrical equipment of a smaller size or rating allowed by the code, if the exact or larger size or rating is not available?
No, only with permission before commencing work.
Source: 2-108, 2-030, CEC, 2021 p73&74
Should pyrotenax cable which has copper sheath be fastened with ordinary conduit or cable strap?
No, possibility of galvanic action
Source: 2-116(2), CEC, 2021 p75
Is a person who has his own source of electrical energy required to obtain a current permit before connecting the installation, alteration or addition to the source although an electrical contractor has done the work?
Yes
Source: 2-016, CEC, 2021 p72
What kind of enclosure would you choose for an installation in a car wash where the electrical equipment may be subjected to direct streams of water?
Table 65 Type 4
Source: 2-400(1)d, CEC, 2021 p79
In hazardous locations where explosives or highly flammable materials or gases are present the code requires a special precaution when repairs or alterations are carried out. What is the precaution?
- Not to be made on live equipement
2-302 and 18-010 - No repairs or alterations shall be carried out on any live equipment
2-304(1)
An installation is subject to drop of falling liquid due to severe condensation. This happens to be indoors. What type of enclosure would you choose?
Table 65 Type 2
2-400(1)b p79
Can NMSC come in contact with metal-clad thermal insulation without violating the rules of this code?
Yes, NMSC may be in contact with the insulation
2-126(1)dii
What does the code say about knob-and-tube wiring in conjunction with metal-clad thermal insulation?
25mm of separation shall be maintained
2-126(1)dii
A 480V motor control centre has exposed live parts. The minimum working space required in front of the exposed live parts is
1m
2-308(4)
What designation of enclosure is required for an indoor dry location where ordinary conditions exist
Type 1
2400(1)a
What does the mark ‘T.E.’ Indicate on a motor nameplate?
Totally enclosed
2-404(1)c
Can a 4-way switch be used as disconnecting means?
No
2-304(2)
A switchboard with exposed live parts is used to supply a 12KV, 3-phase, 4-wire system. What is the minimum working space required for the switchboard?
Take as 12 000 volts to ground ?for year 1)
1,9m
Table 56, 2-308(3)
Which rules is used to reject unapproved electrical equipment?
2-024
2-026
2-100(1)m
In general, what is the maximum voltage to ground permitted for branch ccts in dwelling unit?
150V
2-110