Isolations Flashcards
1
Q
Phase A
A
Manual
SI signal
2
Q
Phase B
A
Manual
2.81 psig Containment Pressure (Hi-Hi)
3
Q
CVI
A
SI signal
Hi-Rad in Cntnmt Purge Exhaust
Manual Phase A or B
4
Q
ABI
A
Manual
Phase A
AB Supp Inlet temp (115F)
HI Rad SFP Area Rad Monitor (ARM) [partial]
5
Q
CRI
A
Manual
SI signal
Hi-Rad in MCR air intake (125/126)
Smoke
6
Q
FWI
A
Rx Trip & Tave < 564F
SI signal
Hi-Hi SG level 82% on 2/3 (inst) in 1/4 (SGs) - P14
Valve Vault flood 2/3 (inst) in 1/2 (rooms)