IP Prep Flashcards

1
Q

Liquid recirculation pump used in an ammonia system is located between

a) compressor and receiver
b) low press receiver and high press receiver
c) low press receiver and evap
d) high press receiver and evap

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

boiling point of r717 ammonia is

a) -28c
b) -27.6c
c) -28f
d) -27f

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When installing globe valves in any system for component isolation. How should they be installed on horizontal line runs

a) valve stem vertical to line run
b) stem horizontal to line run
c) stem any position so long as high pressure side of system is exerted on seat
d) stem should be at right angles

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What component is not normally required in cascade systems?

a) condesner
b) receiver
c) refrigerant flow control on secondary coil
d) low stage condenser

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which type of intercooler is not suitable for ammonia compression systems?

a) dry type
b) shell and coil
c) open type
d) any above are fine

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Multi-stage or booster systems used for very low temp are usually required when compression ratios of a single system exceed

a) 20:1
b) 10:1
c) 3:1
d) 5:1

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Multi stage compression systems can be divided into two major groups which are

a) cascade or extra low
b) cascade or multi stage
c) cascade or direct
d) any above correct

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An ammonia receiver has the following dimensions 3ft x 60inches long. find correct prv

a) 90cuft/min
b) 90lbs/min
c) 7.5cuft/min
d) 7.5lbs/min

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The corrosiveness of a brine and eutectic mixture should maintain between ____ and ___ and can be determined by a ph tester

a) 7 and 6.5
b) 7 and 7.5
c) 7 and 8.5
d) none

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Normal temp drop through low temp chiller is

a) 2 degC at flow rate of 10-15gal/ton
b) 2degF at flow rate of 10-15gal/ton
c) 10degf at flow rate of 2gal/ton
d) 10degc at flow rate of 2gal/ton

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Normally ice temperature is controlled by a brine thermostat (return temp). If your saturated
suction temp is 8 degF what should ice temp be?

a) 18deg f
b) 18deg c
c) 28f
d) 28f

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Centrifugal pumps are widely used, what device can be found in the stuffing box of a pump

a) sleeve bearing
b) ball type bearing
c) mechanical seal
d) packing gland

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Blank

A

Blank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When moisture is present in a refrigeration system, it will react with the refrigerant and the oil to form

a) co2
b) acid
c) co
d) all

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Which of the following represents the lowest vacuum

a) 10psia
b) 5” hg vac
c) 5psig
d) 1000microns

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A compound gayge

a) indicates pressure above 14.696psia
b) indicates pressures in inches hg below atmospheric
c) is one of two gauges on typical manifold
d) all of the above

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

A micron gauge is used to measure

a) atmospheric pressures at high altitudes
b) atmospheric pressures at sea level
c) absolute pressure below 1mm hg
d) high pressure in refrigeration system

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Best method of leak checking is when the refrigeration system is

a) in a vacuum
b) open to atmosphere
c) operating with all fans on
d) standing with dry nitrogen pressure as set in b52

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Non0condensables gases

a) are desirable
b) undesirable
c) condense readily under normal atmospheric conditions
d) help in pulling in a vacuum

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What Is the most accurate instrument for reading a deep vacuum?

a) compound gauge
b) mercury u tube manometer
c) mercury barometer
d) electronic vacuum gayge

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

To insure accurate testing, best material to use for connecting lines to the vacuum pump and gauge set is

a) light flexible hoses
b) heavy duty rubber gauge line
c) copper tube
d) garden hose

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Multiple evacuation means that

a) you connect there pumps simultaneously
b) pull a vacuum on 3 diff systems
c) pull vacuum on same system more than once with nitrogen purging between each

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Moisture in a liquid state must be _____ before it can be removed with a vacuum pump

a) vaporized
b) condensed
c) cooled
d) solidified

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Which of the following refrigerants is a CFC-type refrigerant

a) r22
b) r-123
c) r-134a
d) r-12

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Which of the following is an example an HCFC refrigerant

a) r12
b) r402
c) r22
d) r-134a

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

To re-process refrigerant to meet new product specs is called

a) recovery
b) renew
c) reclaim
d) recycle

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Refrigerants that are made up of two refrigerants that when blended in the right proportions , combine to make a third stable refrigerant, are called

a) blends
b) azeotropes
c) near azeotropes
d) mixtures

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

If a critically charged refrigeration system is over charged , which of the following is a likely result

a) increased cooling capacity
b) reduced compressor discharge temp
c) increased system efficiency
d) increased operating pressures

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

Fractionation occurs when

a) some of a blended refrigerant evaporates or condenses before the rest of the blend
b) fraction of total charge is added
c) operating pressures of a system increase
d) both a and c

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

When charging with a near-azeotropic mixture, what must be done to prevent liquid from entering the system?

a) charge only as vapour through high side
b) charge only liquid through high side
c) charge as liquid through low side using a restrictor
d) charge as a vapour through the low side using a restrictor

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

Charging a refrigeration system refers to

a) removing refrigerant from system
b) adding refrigerant to a system
c) cleaning the refrigerant
d) vaporizing the refrigerant

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

if 22oz is to be added, and supply cylinder weighs 24lb 12oz, what will supply cylinder weigh after?

a) 23lb 12oz
b) 23lb 6oz
c) 22lb 8oz
d) 22lb 6oz

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

if 30oz is to be added to system and cylinder weighs 26lb 4oz before any added. what will supply cylinder weigh after?

a) 22lb 80z
b) 24lb 60z
c) 24lb 80z
d) 22lb 6oz

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

Refrigerant in liquid form is usually put into the system through

a) liquid line
b) suction line
c) hot gas line
d) liquid return line

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

refrigerant in vapour form is usually put into the system through the

a) liquid line
b) suction line
c) hot gas line
d) liquid return line

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

when charging refrigerant system with vapour from a cylinder, the cylinder will become

a) cold
b) very warm
c) same temp as ambient
d)

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q

When charging liquid refrigerant from a single valve supply cylinder, the cylinder is placed

a) upside down
b) right side up
c) on its side
d) in any position

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q

a graduated cylinder charging device is a device that

a) measures refrigerant by volume for precise charge
b) compensation dial for adjusting temp of freon
c) heater keeps freon temp from dropping when released into system,
d) all of the above

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

Factory r22 split shows 6lb 8oz in outdoor condensing unit and 2oz in evap. The 3/8 liquid line contains .48oz per foot and 7/8 suction line contains .10oz per foot . Lines are 30ft long. What is correct charge?

a) 6lb 10oz
b) 6lb 15oz
c) 7lb 7oz
d) 7lb 11oz

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
40
Q

to pull a vacuum means to

a) raise pressure in refrigeration system
b) lower pressure in refrigeration system
c) lower pressure in refrigeration system below atmosphere
d) condense gases

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
41
Q

liquid freon charging should be done when refrigeration system is

a) off and introduced through SSV
b) very low on freon
c) on and introduced through compressor service valves as long as they are front seated
d) off and introduced through the king valve on liquid receiver

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
42
Q

TW=20lb and WC=35lb. How much freon can be recovered to tank if you used liquid lift recovery method without oil separation.

a) 33lb
b) 21lb
c) 28lb
d) 35lb

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
43
Q

When using a recovery unit on a system needing repair, normal sequence goes

a) recover, repair, evacuate, recharge
b) recover, repair, pressure test, evacuate, recharge
c) recover, repair, evacuate, pressure test, recharge
d) any combo

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
44
Q

Best way to determine charge on unit with no gas and no sight glass is

a) using two lb per ton design cooling
b) pressure method of charging
c) superheat method
d) old ads equipment log if available

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
45
Q

control can be which of the following?

a) electrical
b) mechanical
c) electrical and mechanical
d) all of the above

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
46
Q

example of a power consuming device would be a ____ while an example of a non-power consuming device is a ____

a) SPST switch, light bulb
b) light bulb, elec motor
c) elec motor, light bulb
d) light bulb, SPST switch

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
47
Q

Air con system turned on but no major components turn on; comp, fans, etc. Check first

a) compressor wires
b) indoor fan relay
c) condenser fan motor capacitor
d) power being supplied to system

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
48
Q

Transformers are rated using

a) volt-amperes
b) volt-ohms
c) amperes-ohms
d) volt-resistance

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
49
Q

Air con system calling for cooling and comp is running but indoor fan is not. Which terminal on stat do you check first?

a) Y
b) G
c) R
d) W

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
50
Q

An electrical power consuming component is usually

a) wired in series
b) to pass power to another component
c) often a basic switch
d) uses power and is wired in parallel

A

d

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
51
Q

line side of a switch is

a) side load is connected to
b) neutral side of circuit
c) side of power source
d) side with white wire

A

c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
52
Q

continuity through a heat relay is checked with

a) ohmeter
b) voltmeter
c) clamp on meter
d) micron gauge

A

a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
53
Q

a ten wrap amperage multiplier is used with a

a) volt meter
b) clamp on ammeter
c) ohmmeter
d) megger

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
54
Q

A ________ is the easiest diagram to use to follow a cct. circuit function is obvious

a) pictorial
b) ladder
c) layout
d) oblique

A

b

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
55
Q

An electrical diagram showing the approx location of components is called a

a) pictorial
b) ladder
c) layout
d) oblique

A

a

56
Q

Process of ice making usually occurs in what temp range?

a) 0-5f
b) 5-20f
c) -10 - 0f
d) 20-30f

A

b

57
Q

If an air cooled condenser is located on a 95F roof and con sat temp is 150f, which of following is likely

a) overcharge
b) condenser clogged
c) system undercharged
d) both a and b correct

A

d

58
Q

An air cooled R12 operating good with 25psig suction and 136psig head. which represents possible pressures if condenser fan motor burns out

a) high side 136 low side 25
b) high side 100 low side 15
c) high side 200 low side 20
d) high side 180 low side 35

A

d

59
Q

In a waste water system the water in the condenser is 85f and leaving is 105f. Which is logical explanation for conditions above

a) reduced water flow through con
b) scale build up in water
c) excess water through con
d) Both a and b

A

a

60
Q

In a waste water system the water in the condenser is 85f and leaving is 90F. Which is logical explanation for conditions above

a) reduced water flow through con
b) scale build up in water
c) excess water through con
d) Both b and c

A

d

61
Q

Ref cabinet temp of a high temp fridge unit ranges from

a) 75-95f
b) 60-75f
c) 45-60F
d) 25-45f

A

c

62
Q

high temp ref unit the boiling point of freon in the coil is normally ______ lower than the cabinet temp

a) 10-20f
b) 25-35f
c) 35-46f
d) 5 - 15f

A

a

63
Q

Medium temp ref cabinet range from

a) 5-20f
b) 20-35f
c) 35-50f
d) 30-45f

A

d

64
Q

condensing units located outside that operate year round

a) larger fan motors
b) cpr valves
c) all weather protection
d) head pressure control

A

d

65
Q

with entering air to condenser above 70f, the td between outdoor air and condensing temp on standard units will be?

a) 10-15f
b) 15-20f
c) 20-25f
d) 25-30f

A

d

66
Q

When the comp in a system using cap tubes is sweating it is a sign of

a) overcharge
b) dirty evap
c) evap blower motor problem
d) any above

A

d

67
Q

In a waste water cooled system, the diff between condensing temp of freon and leaving water is approx

a) 10f
b) 20f
c) 30f
d) 40f

A

a

68
Q

in a water cooled condensing unit/ cooling tower combo, the td of water through the condenser will be approx

a) 10f
b) 20f
c) 30f
d) 40f

A

a

69
Q

approach of a cooling tower is

a) diff between entering and leaving wet bulb temperatures
b) number of degrees water is cooled in the tower
c) diff in temp between the entering air wet bulb and sump water temp
d) diff in temp between the entering air wet bulb and water entering tower

A

c

70
Q

Completely clogged driers can lead to?

a) low evap fan amperage
b) compressor damage
c) evap ice formation
d) all of the above

A

d

71
Q

if the blades of a forward curved centrifugal (evap) blower become clogged with dirt, what is likely

a) evap could freeze
b) suction pressure drops
c) head would rise
d) both a and b

A

d

72
Q

Standard air con system will operate with an evap boiling point of

a) 40
b) 45
c) 50
d) 55

A

a

73
Q

in a system using cap tube or orifice , when the air filters become clogged, SH will

a) increase
b) decrease
c) remain same
d) swing back n forth

A

b

74
Q

in a system using a txv , when air filters become restricted, SH will

a) increase
b) decrease
c) remain same
d) disappear

A

c

75
Q

when is it beneficial to pump down a system before servicing?

a) when comp needs to be changed
b) when txv needs changing
c) when condenser needs cleaning
d) condenser coil needs replacing

A

b

76
Q

As a rule of thumb: air leaving evap will be about ______ than air entering

a) 17-20 warmer
b) 10-15 warmer
c) 17-20 cooler
d) 10-15 cooler

A

c

77
Q

if compressor motor locks up it will_____

a) not start
b) hum then turn off
c) draw RLA
d) all of the above

A

d

78
Q

A service valve can be used to

a) check electrical service to comp
b) isolate ref so system can be serviced
c) check air flow across evap
d) ambient air check

A

b

79
Q

on a 95f day, r22 pressure on high side should be about

a) 182
b) 108
c) 297
d) 243

A

b

80
Q

liquid line temp is used to determine _____ of condenser

a) superheat
b) low side press
c) suction pressure
d) sub cooling

A

d

81
Q

to accurately add freon, condenser ambient temp of about ______f should be simulated

a) 75
b) 85
c) 95
d) 100

A

c

82
Q

instrument used to check for a short in the compressor winding is called a

a) ohmmeter
b) ammeter
c) voltemeter
d) milliamp meter

A

a)

83
Q

problems in refrigeration portion of the system are caused by

a) refrigerant quantity
b) ref flow
c) contaminents
d) any of above

A

d

84
Q

typical evap superheat reading at evaporator outlet for central air on a 95f day would be

a) 5-7
b) 8-10
c) 10-12
d) 12-15

A

c

85
Q

After repairing a system that has had an electrical motor failure (comp burnout). It is good field practice to re-use the recovered refrigerant in that system?

a) true
b) false

A

false

86
Q

air entering a refrigerant system can eventually lead to compressor failure

a) true
b) false

A

true

87
Q

clearance tolerances are such that the ordinary clean refrigerant oil can be used satisfactorily in a vacuum pump

a) true
b) false

A

false

88
Q

while under deep vacuum , any liquid water under oil in the motor compressor assembly can be removed by operating compressor motor for several seconds without any adverse affect on system

a) true
b) false

A

false

89
Q

rec max pressure for leak testing is 150psig

a) true
b) false

A

false

90
Q

s it possible to have a leak free system when under a vacuum but still leak when the system pressure is above atmospheric

a) true
b) false

A

true

91
Q

pressure test of 100 microns has been reached with vacuum pump on. pump is turned off and gauge reading rises above 500 microns, this indicates a leak

a) true
b) false

A

true

92
Q

Azeotropic mix will separate into its components and have specific separate boiling points. A near azeo mix will not separate readily. This causes glide. Near mixtures must be removed from their container n the liquid form to prevent fractionalization

a) true
b) false

A

false

93
Q

Fractionalization is when parts of (refrigerants) of a nearazeotrpic mixture condense and or evaporate at different rates

a) true
b) false

A

true

94
Q

Glide is the range of pressures/temperatures in which a blended refrigerant will condense

a) true
b) false

A

true

95
Q

one god feature on an electric charging scale is that It counts upwards as refrigerant is removed , to tell the technician how much was used

a) true
b) false

A

true

96
Q

quickest method to charge is doing vapour only

a) true
b) false

A

false

97
Q

when adding freon in vapor form to a ref system, system motor/comp is running

a) true
b) false

A

true

98
Q

when adding freon in liquid form into the high side, system compressor/ motor is running

a) true
b) false

A

false

99
Q

using a restrictor, liquid freon can be charged into low side of system with system on

a) true
b) false

A

true

100
Q

manuf charging chart may be used when available to determine correct charge for a system

a) true
b) false

A

true

101
Q

a deep vacuum involves reducing pressure in system to approx 50-100 microns. with a field acceptable level of 500

a) true
b) false

A

true

102
Q

Nitrogen is an inert gas used to test refrigeration systems for leaks

a) true
b) false

A

true

103
Q

freon driers are commonly used to remove any moisture left in system after install r servicing has been performed . a type of desiccant used in these driers is silica gel which is an adsorbent?

a) true
b) false

A

false

104
Q

when referring to vac depth “deep and high” vacuum mean the same thing

a) true
b) false

A

true

105
Q

when adding oil to a refrigeration compressor w/ a sight glass, oil level upon completion should be 3/4 way up with comp off according to manuf rec

a) true
b) false

A

true

106
Q

a halide leak detector can be used with a mixture of nitrogen and sulfur hexafluoride to indicate leaks

a) true
b) false

A

false

107
Q

when servicing a ref system when it is short of both freon and oil, ref should be added first then top up oil as req’d

a) true
b) false

A

true

108
Q

if line one of a circuit had a potential of 120v and line two was neutral , the potential voltage between line on and two would be zero volts

a) true
b) false

A

false

109
Q

heating anticipator in a thermostat is usually of the adjustable type

a) true
b) false

A

true

110
Q

cooling anticipator is usually of the adjustable type

a) true
b) false

A

false

111
Q

when checking thermostat circuits an insulated jumper wire is a handy tool

a) true
b) false

A

true

112
Q

a 120v/24v control transformer has a VA of 20 . Max amp the transformer will put out is .8 amps

a) true
b) false

A

true

113
Q

regardless of what load is on sec side of transformer, output voltage remains the same

a) true
b) false

A

false

114
Q

when using a ten -wrap multiplier, reading on the meter must be multiplied by ten

a) true
b) false

A

false

115
Q

while troubleshooting a 24v circuit w thermostat, press control, contactor coil, tech reads 24v across stat, 0v on press control, 0v across coil. technician says this

  • transformer burned out
  • stat is open
  • contactor coil is energized
    a) true
    b) false
A

false

116
Q

since any new replacement refrigerants are being used, a tech should rely on system temperatures to ease troubleshooting

a) true
b) false

A

true

117
Q

a txv capacity will drop if if pressure drop across the valve increases

a) true
b) false

A

false

118
Q

high comp ratios lead to lower compressor discharge temps

a) true
b) false

A

false

119
Q

bubbles in sight glass always indicates low charge

a) true
b) false

A

false

120
Q

best place for liquid line sight glass is the inlet of expansion device

a) true
b) false

A

true

121
Q

Low density vapours entering the compressor mean low refrigerant flow through compressor

a) true
b) false

A

true

122
Q

because of low freon flow through compressor and low charge, the 100% saturated vapour point in condenser will be very low, causing low SC

a) true
b) false

A

true

123
Q

dirty condenser coils are often the cause for inefficient compressors
a) true
b) false

A

true

124
Q

if the evap and compressor are starved, condenser will also be starved

a) true
b) false

A

true

125
Q

since evap absorbs both sensible and latent heat, humidity must be taken into account and considered as part of the load on the evap

a) true
b) false

A

true

126
Q

high eff condensers can actually be too efficient on cool days

a) true
b) false

A

true

127
Q

temp drop in air through evap responds in reverse to a change in cfm through the evap

a) true
b) false

A

true

128
Q

best way to tell if a comp discharge line is correct is to touch it

a) true
b) false

A

false

129
Q

if metering device malfunctions and gets stuck in the closed position, compressor could overheat
a) true
b) false

A

true

130
Q

if a compressor has partially shorted winding it could run for a while, overheat then shut off

a) true
b) false

A

true

131
Q

when checking elec circuits of an air con system, each parallel circuit should be isolated and checked separately

a) true
b) false

A

true

132
Q

with a rise in outdoor temp the head pressure will rise

A

tru

133
Q

superheat occurs in condenser as well as evaporator

a) true
b) false

A

true

134
Q

subcooling occurs in evap as well condenser

true
false

A

false

135
Q

a suction line filter drier should always be installed with a compressor changeout

true
false

A

false