Intial Verification (Before Testing) Flashcards
- Connection of conductors
Ensure all connections are mechanically secure
- use a tug test
- use a torque driver for the connections
- visual examination
- connection too tight causing mechanical damage at the cable
Poor connections can cause arcing, will give a high resistance on r1+r2 test
- Identification of conductors
All conductors to be numbered or coloured to ID the cable
- T&E CPC must have green and yellow sleeving
- The use of sleeving or tape to ID strappers or switch wires
Used to correctly ID line, neutral and CPC for termination conductors.
- Routing of cables
Cables should be placed behind walls in straight lines, cable on the surface should be protected in trunking or conduit.
- Visual inspection of trunking/conduit to ensure it is complete and there is no damage
- Cables behind walls should be examed during consturction
- Cable in a wall must be within 150mm of a corner or ceiling
- Selection of conductors
Cables should be selected to ensure they can carry the current to the load without an overload of excessive volt drop
- Volt drop 3% for lights, 5% for everything else
- Check protective device’s current against the current carrying capacity of the cable
- Check the length of the run with the mV/A/M value of the cable and the load current
- Connection of Single Pole Devices
Visual inspection to ensure on single pole circuits the line conductor (not the neutral) is switched)
- Correct connection of accessories (Polarity)
Visual inspection to ensure the polarity of any connected accessory is correct
- Presence of fire barriers (not for domestic)
Visual inspection of barriers used to block holes for cable runs between areas of buildings that require fire barriers
- Methods of protection agains electric shock A
- SELV - 50v AC without an earth
- PELV - 50v AC or below with earth
- Visual inspection of transformer to ensure it is correctly rated
- Visual inspection to ensure correct earthing arrangement is present
- Double insulation - 2 layers of PVC, visual inspection to ensure there are no cracks
- Methods of protection agains electric shock B - Basic Protection
- Physical inspection of insulation of live parts and insulation around the cable to ensure there is no exposed conductor
- Visual inspection to ensure adequate protection by barrier or enclosure and protection of PVC single core cable using trunking or conduit, preventing them from being touched
- Visual inspection to ensure enclosure is complete and undamaged
- Physical inspection to ensure there are barriers over exposed bars preventing touch
- Methods of protection agains electric shock C - Fault Protection
Alternative sources
- Ensure there are no alternative sources such as solar panels, make sure there is additional isolation if they are present
Setting of protective devices
- Ensure the correct circuit breaker and overload rely are present
- Ensure the correct rating of protective devices is used
- Overload relys should be set to the current rating of the motor
Automatic disconnetion of the supply
Earth fault loop impedence
- A low impedence is needed to give a high fault current, the large over current flows through the circuit rupturing the protective device in 0.4 or 5s
- If earth loop impedance value is to high the circuit will either take to long to trip or won’t trip at all
Earthing arrangements
Earth electrode - visual inspection of earth rod
Earthing conductor - earth supply from supply company
Circuit protective conductor - visual inspection of CPC
Protective bonding conductor - visual inspection
Supplementary bonding conductors - visual inspection
Exposed conductive parts are connected to earthing arrangements - visual inspection
Electrical seperation
Protection through a transformer where the earth stops on the primary side
- must be used in bathrooms
Additional protection RCDs
must be a 30mA RCD - visual inspection
Prevention of mutual detrimental influence
Visual inspection to ensure -
Seperation of electrical cables and telecom cables
Consumer units should be away from water pipes