Intial Verification (Before Testing) Flashcards

1
Q
  1. Connection of conductors
A

Ensure all connections are mechanically secure
- use a tug test
- use a torque driver for the connections
- visual examination
- connection too tight causing mechanical damage at the cable
Poor connections can cause arcing, will give a high resistance on r1+r2 test

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  1. Identification of conductors
A

All conductors to be numbered or coloured to ID the cable
- T&E CPC must have green and yellow sleeving
- The use of sleeving or tape to ID strappers or switch wires
Used to correctly ID line, neutral and CPC for termination conductors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  1. Routing of cables
A

Cables should be placed behind walls in straight lines, cable on the surface should be protected in trunking or conduit.
- Visual inspection of trunking/conduit to ensure it is complete and there is no damage
- Cables behind walls should be examed during consturction
- Cable in a wall must be within 150mm of a corner or ceiling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. Selection of conductors
A

Cables should be selected to ensure they can carry the current to the load without an overload of excessive volt drop
- Volt drop 3% for lights, 5% for everything else
- Check protective device’s current against the current carrying capacity of the cable
- Check the length of the run with the mV/A/M value of the cable and the load current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. Connection of Single Pole Devices
A

Visual inspection to ensure on single pole circuits the line conductor (not the neutral) is switched)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  1. Correct connection of accessories (Polarity)
A

Visual inspection to ensure the polarity of any connected accessory is correct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  1. Presence of fire barriers (not for domestic)
A

Visual inspection of barriers used to block holes for cable runs between areas of buildings that require fire barriers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  1. Methods of protection agains electric shock A
A
  • SELV - 50v AC without an earth
  • PELV - 50v AC or below with earth
  • Visual inspection of transformer to ensure it is correctly rated
  • Visual inspection to ensure correct earthing arrangement is present
  • Double insulation - 2 layers of PVC, visual inspection to ensure there are no cracks
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  1. Methods of protection agains electric shock B - Basic Protection
A
  • Physical inspection of insulation of live parts and insulation around the cable to ensure there is no exposed conductor
  • Visual inspection to ensure adequate protection by barrier or enclosure and protection of PVC single core cable using trunking or conduit, preventing them from being touched
  • Visual inspection to ensure enclosure is complete and undamaged
  • Physical inspection to ensure there are barriers over exposed bars preventing touch
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  1. Methods of protection agains electric shock C - Fault Protection
A

Alternative sources
- Ensure there are no alternative sources such as solar panels, make sure there is additional isolation if they are present
Setting of protective devices
- Ensure the correct circuit breaker and overload rely are present
- Ensure the correct rating of protective devices is used
- Overload relys should be set to the current rating of the motor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Automatic disconnetion of the supply

A

Earth fault loop impedence
- A low impedence is needed to give a high fault current, the large over current flows through the circuit rupturing the protective device in 0.4 or 5s
- If earth loop impedance value is to high the circuit will either take to long to trip or won’t trip at all

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Earthing arrangements

A

Earth electrode - visual inspection of earth rod
Earthing conductor - earth supply from supply company
Circuit protective conductor - visual inspection of CPC
Protective bonding conductor - visual inspection
Supplementary bonding conductors - visual inspection
Exposed conductive parts are connected to earthing arrangements - visual inspection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Electrical seperation

A

Protection through a transformer where the earth stops on the primary side
- must be used in bathrooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Additional protection RCDs

A

must be a 30mA RCD - visual inspection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Prevention of mutual detrimental influence

A

Visual inspection to ensure -
Seperation of electrical cables and telecom cables
Consumer units should be away from water pipes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Presence of appropriate devices for isolation and switching correctly located

A

visual inspection to ensure devices are there and appropriately located

17
Q

Presence of undervoltage protection devices (not domestic)

A

For specalist areas, particularly used with 3ph motors, when these motors are switched on they can induce a volt drop which would increase current potentially tripping the supply breaker, these sense the volt drop and trip before it happens.
Visual inspection

18
Q

Labelling of protective devices, switches

A

Visual inspection to ensure correct labelling is in place

19
Q

Selection of equipment and protective measures appropriate to external influences

A

Entrances for vermin should be filled particularly holes for cables to enter buildings

20
Q

Adequacy of access to switchgear and equipment (including consumer unit)

A

Access to switch gear should not be restricted, doors open to 90
Consumer unit front face should be able to be open and be removed

21
Q

Presence of danger notices and other warnings

A

Visual inspection of test date labels, earth clamps label, voltage warning for 400v or higher

22
Q

Presence of diagram, instructions and similar info

A

3 main drawings - lighting, power, containment
OM (operating and maintenance manual)

23
Q

Selection and erection of wiring systems

A

Visual inspection to ensure trunking, conduit or containment has been correctly installed and that metal conduit or trunking has an earth link.

24
Q

Selection and installation of suitable surge protection device

A

visual inspection to ensure SPD is there is necessary.