External Earth Fault Loop Impedance (Ze) Flashcards

1
Q

Where is it measured and why?

A

Measured at the supply as this is where the impedance will be lowest

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What can it be used for?

A

Gives the Ze value which can be used to calculate the Zs of all circuits (Zs=Ze+r1-r2), this allows all earth loop impedance values can be calculated dead. Meaning only one live test has to be carried out

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Why are Zs values required

A

Required to ensure all protective devices can operate within their required time constraints of 0.4s for 32A or less or sockets up to 63A and everything else is allowed 5s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What can this be used to calculate?

A

Earth loop impedance can be used to calculate the prospective fault current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly